6ES7431-7KF10-0AB0 SIMATIC S7-400 analog input module with 8 AI, 16-bit resolution, resistance and RTD inputs, diagnostics alarm, and 20 ms conversion time. Check a legacy part request.

Complete Product Information
Product Code
6ES7431-7KF10-0AB0
Dimensions
29.8 × 23.5 × 4.3 cm
Weight
0.761 kg
Lifecycle
Announcement of product phase-out
Availability
Check availability with quotation
Lead Time
Confirmed with quotation
Product Attachment
Download technical file

Availability, lead time, condition and warranty are confirmed for each quotation.

Product Information

Technical Product Information

Product Description

Key Features

  • Analog input capacity: 8 analog inputs, including 8 inputs for resistance measurement.
  • Resolution and conversion: Resolution with overrange is 16 bit; integration time is 20 ms at 50 Hz for the entire module including wire break.
  • Supported input types: Resistance thermometer and resistance inputs are supported; voltage, current and thermocouple input ranges are not supported.
  • RTD support: Pt100, Pt1000, Pt200, Pt500, Ni100 and Ni1000 are supported, with selectable Europe/U.S. characteristics for Ni1000 and Ni100.
  • Diagnostics and alarms: Diagnostics, diagnostic alarms and hardware interrupts are parameterizable; limit value alarms are supported.
  • Lifecycle data: Product lifecycle: Announcement of product phase-out.

Applications

  • Resistance measurement: Measures resistance using two-wire or three-wire signal-encoder connections.
  • Resistance thermometer measurement: Measures resistance thermometers including Pt100, Pt1000, Pt200, Pt500, Ni100 and Ni1000.

Technical Summary

Product type SIMATIC S7-400 analog input SM 431
Analog inputs 8
Resolution with overrange 16 bit
Integration time 20 ms at 50 Hz (entire module incl. wire break)
Basic conversion time 8 / 23 / 25 ms
Resistance thermometer types Pt100, Pt1000, Pt200, Pt500, Ni100, Ni1000
Constant measurement current 1 mA, typ.
Diagnostics function Yes; Parameterizable
Diagnostic alarm Yes; Parameterizable
Potential separation Between the channels and backplane bus: Yes; between the channels: No
Product lifecycle Announcement of product phase-out

Frequently Asked Questions

How many analog inputs does 6ES7431-7KF10-0AB0 have?

It has 8 analog inputs, including 8 inputs for resistance measurement.

Which resistance thermometers are supported?

It supports Pt100, Pt1000, Pt200, Pt500, Ni100 and Ni1000.

What resolution and integration time does the module provide?

Resolution with overrange is 16 bit, and integration time is 20 ms at 50 Hz for the entire module including wire break.

Does the module provide diagnostics and alarms?

Yes. Diagnostics and diagnostic alarms are parameterizable, and limit value alarms are supported.

Product Information

RFQ Information

When contacting us by email, include the model or part number, quantity, brand, specifications and destination. Product or nameplate photos can help identify the requested item.

01Which product reference should I send?

Send the complete model, order number or MLFB shown on the product. Include the hardware version when it matters.

02How are supply terms confirmed?

Availability, condition, lead time, warranty and delivery terms are stated for the specific quotation.

03What helps with replacement requests?

Share the installed model, application, electrical and mechanical requirements, communication interface and a clear nameplate photo.

Product RFQ

Send the Details Needed for a Quotation

Use the form for the product model, quantity and contact details. Add the destination and technical questions in the message.

When contacting us by email, include the model or part number, quantity, brand, specifications and destination. Product or nameplate photos can help identify the requested item.

Email Your Requirement

* Email is required. Other fields are optional, but more detail helps us respond accurately.

Request a Quote