Product Description
Key Features
- Digital output identity: SIMATIC S7-400 SM 422 digital output module with isolated 16 DO.
- Load voltage: Rated load voltage: 230 V; 120/230 V AC. Permissible range: 79 V to 264 V, with a permissible frequency range of 47 Hz to 63 Hz.
- Output current: Signal "1" output current: 2 A rated value, with a permissible range of 10 mA to 2 A and permissible surge current of 50 A per cycle.
- Output protection: Short-circuit protection: Yes; clocked electronically. Following a short-circuit, reclosing under a full load cannot be ensured.
- Channel separation: Digital outputs have potential separation between channels and between channels and the backplane bus; separation is in groups of 4.
- Lifecycle status: Announcement of product phase-out.
Applications
- Redundant load control: Two outputs can be switched in parallel for redundant control of a load, only with outputs having the same load voltage.
- Digital input control: The digital outputs can control a digital input.
Technical Summary
| Digital outputs | 16 |
|---|---|
| Rated load voltage | 230 V; 120/230 V AC |
| Output current for signal "1", rated value | 2 A |
| Output current for signal "1", permissible range | 10 mA to 2 A |
| Response time, max. | 100 ms |
| Short-circuit protection | Yes; Clocked electronically: Following a short-circuit, reclosing under a full load cannot be ensured. |
| Potential separation | Between channels and between channels and backplane bus; in groups of 4 |
| Switching capacity on lamp load, max. | 50 W |
| Product lifecycle | Announcement of product phase-out |
Frequently Asked Questions
What exact model should be confirmed for this digital output module?
Confirm Siemens 6ES7422-1FH00-0AA0, SIMATIC S7-400 SM 422, with isolated 16 DO.
What load voltage does the module use?
The rated load voltage is 230 V; 120/230 V AC. The permissible range is 79 V to 264 V at 47 Hz to 63 Hz.
What is the output current range?
For signal "1", the rated output current is 2 A, with a permissible range of 10 mA to 2 A.
Does the module have short-circuit protection?
Yes; protection is clocked electronically. Following a short-circuit, reclosing under a full load cannot be ensured.
What lifecycle information should be considered?
The product lifecycle information is Announcement of product phase-out. Confirm the requested quantity, destination, and condition preference.