Product Description
Key Features
- Exact product identity: SIPLUS S7-300 SM 322-20-pole based on 6ES7322-8BF00-0AB0, with conformal coating.
- Digital outputs: The module has 8 digital outputs with electronic short-circuit protection.
- Load voltage: Rated load voltage L+ is 24 V DC, with a permissible range of 20.4 V to 28.8 V DC.
- Output current: Rated output current for signal "1" is 0.5 A; the permissible range is 10 mA to 0.6 A for 0 to 40 °C and 40 to 60 °C.
- Diagnostics: Diagnostics are parameterizable; wire break, short-circuit, and missing load voltage can be diagnosed. Fuse blown detection is not available.
- Installation and isolation: The module supports horizontal and vertical installation, with potential separation between the channels in groups of 8 and optocoupler separation from the backplane bus.
Applications
- Digital input control: The outputs can control a digital input.
Technical Summary
| Order number | 6AG1322-8BF00-2AB0 |
|---|---|
| Product family | SIPLUS S7-300 SM 322-20-pole |
| Based on | 6ES7322-8BF00-0AB0 |
| Digital outputs | 8 |
| Rated load voltage L+ | 24 V DC |
| Permissible load voltage L+ | 20.4 V to 28.8 V DC |
| Rated output current for signal "1" | 0.5 A |
| Diagnostics | Parameterizable; wire break, short-circuit, and missing load voltage |
| Potential separation | Between channels in groups of 8; optocoupler separation from backplane bus |
| Product lifecycle | Product cancellation |
Frequently Asked Questions
What exact code should be confirmed for this SIPLUS module?
Confirm order number 6AG1322-8BF00-2AB0 and the based-on code 6ES7322-8BF00-0AB0.
How many digital outputs does 6AG1322-8BF00-2AB0 have?
It has 8 digital outputs with electronic short-circuit protection.
What load voltage does the module require?
Rated load voltage L+ is 24 V DC, with a permissible range of 20.4 V to 28.8 V DC.
What should be confirmed for a legacy-part request?