Product Description
Key Features
- Exact product identity: Product type designation: Active Backplane ST 1+4 Slot; based on 6ES7590-0BD00-0AA0.
- Active backplane bus: 5 slots for inserting S7-1500 I/O modules for hot swapping in the ET 200MP with IM 155-5 PN HF from FW V4.4.1.
- Power and firmware: Power consumption from the backplane bus: 2 W. FW update possible: Yes.
- Conformal coating: Conformal coating for printed circuit board assemblies according to EN 61086: Class 2 for high reliability; protection against fouling according to EN 60664-3: Type 1 protection.
- Installation temperature: Ambient temperature during operation: -40 °C to 70 °C for horizontal installation; -40 °C to 40 °C for vertical installation. Horizontal installation supports +85 °C for 10 min under OT4, ST1/ST2 according to EN 50155.
- Dimensions and weight: Dimensions: 154 mm width, 99 mm height, 14 mm depth. Weight, approx.: 127 g.
Applications
- Hot swapping in ET 200MP: Inserting S7-1500 I/O modules for hot swapping in the ET 200MP with IM 155-5 PN HF from FW V4.4.1.
Technical Summary
| Product type designation | Active Backplane ST 1+4 Slot |
|---|---|
| Order number | 6AG2590-0BD00-4AA0 |
| Based on | 6ES7590-0BD00-0AA0 |
| Number of slots | 5 |
| Power consumption from the backplane bus | 2 W |
| FW update possible | Yes |
| I&M data | Yes; I&M0 to I&M3 |
| Isochronous mode | Yes |
| Prioritized startup | Yes |
| Horizontal installation temperature | -40 °C to 70 °C; +85 °C for 10 min (OT4, ST1/ST2 according to EN 50155) |
| Vertical installation temperature | -40 °C to 40 °C |
| Product lifecycle | Active Product |
Frequently Asked Questions
What is the exact order number of this Siemens SIPLUS backplane?
The exact order number is 6AG2590-0BD00-4AA0.
How many slots does the Active Backplane ST 1+4 Slot have?
It has 5 slots.
What operating temperature applies to horizontal installation?
The ambient temperature during operation is -40 °C to 70 °C for horizontal installation; +85 °C is supported for 10 min under OT4, ST1/ST2 according to EN 50155.
What firmware condition is supplied for ET 200MP use?
Use in the ET 200MP with IM 155-5 PN HF is supported from FW V4.4.1.