Product Description
Key Features
- Exact product identity: SIPLUS ET 200SP BU15-P16+A0+2D/T TX rail based on 6ES7193-6BP00-0DA1; BU type A1.
- Supply and current capacity: Rated supply: 24 V DC. Maximum current carrying capacity: 10 A for the P1 and P2 bus and 2 A for process terminals.
- Connection configuration: Push-in terminals; 16 process terminals to the I/O module and 2 terminals with connection to the P1 and P2 bus. AUX and add-on terminals do not exist.
- Conformal coating and protection: Conformal coating according to EN 61086 Class 2 for high reliability; Type 1 protection according to EN 60664-3.
- Installation and dimensions: Width: 15 mm; height: 117 mm; depth: 35 mm. One slot, Type A1; new potential group.
- Temperature and lifecycle: Product lifecycle: Active Product. Ambient temperature during operation is -40 °C to 70 °C for horizontal installation, with +85 °C for 10 minutes under OT4, ST1/ST2 according to EN 50155.
Applications
- Railway applications: The product supports railway applications, including EMC for rail vehicles, signal and telecommunications systems, fixed installations, and railway power supply equipment.
- Industrial process technology: The product is specified for environmental conditions in industrial process technology according to EN 60654-4 and ANSI/ISA-71.04.
Technical Summary
| Product model | 6AG2193-6BP00-4DA1 |
|---|---|
| Product family | SIPLUS ET 200SP BU15-P16+A0+2D/T TX rail |
| Based on | 6ES7193-6BP00-0DA1 |
| Product type | BU type A1 |
| Rated supply | 24 V DC |
| Maximum P1 and P2 bus current | 10 A |
| Maximum process-terminal current | 2 A |
| Terminal type | Push-in terminal |
| Process terminals | 16 |
| Product lifecycle | Active Product |
Frequently Asked Questions
What order number should be confirmed for this Siemens SIPLUS ET 200SP BaseUnit?
Confirm the complete order number 6AG2193-6BP00-4DA1 and the based-on reference 6ES7193-6BP00-0DA1.
What terminal configuration does 6AG2193-6BP00-4DA1 have?
It has push-in terminals, 16 process terminals to the I/O module, and 2 terminals with connection to the P1 and P2 bus. AUX and add-on terminals do not exist.
What supply and current ratings should be checked?
The rated supply is 24 V DC. Maximum current carrying capacity is 10 A for the P1 and P2 bus and 2 A for process terminals.
What installation temperature range applies?
For horizontal installation, the ambient temperature during operation is -40 °C to 70 °C, with +85 °C for 10 minutes under OT4, ST1/ST2 according to EN 50155. For vertical installation, it is -40 °C to 50 °C.