Product Description
Key Features
- Analog output identity: Product type designation: AQ 4xU/I ST, with 4 analog outputs.
- Supply and protection: Rated supply: 24 V DC; permissible range: 19.2 V to 28.8 V DC; reverse polarity protection: Yes.
- Output ranges and resolution: Voltage ranges include 0 to 10 V, 1 V to 5 V, -5 V to +5 V and -10 V to +10 V; current ranges include 0 to 20 mA, -20 mA to +20 mA and 4 mA to 20 mA; resolution: up to 16 bit.
- BaseUnit and coding: Usable BaseUnits: BU type A0, A1. Automatic encoding and a Type A mechanical coding element are provided; color code: CC00.
- Diagnostics and firmware: Module diagnostics, diagnostic alarms, supply-voltage monitoring, wire-break and short-circuit diagnosis are provided. FW update possible: Yes; I&M0 to I&M3 are supported.
Technical Summary
| Product | 6AG2135-6HD00-4BA1 |
|---|---|
| Product type | AQ 4xU/I ST |
| Supply voltage, rated value (DC) | 24 V |
| Permissible supply voltage range (DC) | 19.2 V to 28.8 V |
| Number of analog outputs | 4; > +60 °C max. 2x ±10 V permissible |
| Resolution with overrange | 16 bit |
| Cycle time (all channels), min. | 5 ms |
| Usable BaseUnits | BU type A0, A1 |
| Ambient temperature, horizontal installation | -40 °C to +70 °C; +85 °C for 10 min (OT4, ST1/ST2 acc. to EN 50155) |
| Product lifecycle | Active Product |
Frequently Asked Questions
What order number identifies this Siemens module?
The exact order number is 6AG2135-6HD00-4BA1, with product type AQ 4xU/I ST.
What supply voltage does the module require?
The rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
Which BaseUnits and output ranges are supported?
Usable BaseUnits are BU type A0 and A1. Supported ranges include 0 to 10 V, 1 V to 5 V, -5 V to +5 V, -10 V to +10 V, 0 to 20 mA, -20 mA to +20 mA and 4 mA to 20 mA.
Does the module provide diagnostics and firmware updates?
Yes. It provides module diagnostics, diagnostic alarms, supply-voltage monitoring, wire-break and short-circuit diagnosis, and FW update is possible.