Product Description
Key Features
- Exact module identity: SIPLUS ET 200SP AI 4xI 2-/4-wire ST analog input module, based on 6ES7134-6GD01-0BA1.
- Analog input capacity: 4 analog inputs; above 60 °C, maximum 1x ±20 mA is permissible.
- Input ranges and resolution: Supports 0 to 20 mA with 16 bit including sign, -20 mA to +20 mA, and 4 mA to 20 mA with 15 bit.
- Supply and encoder output: Rated supply: 24 V DC, permissible range: 19.2 V to 28.8 V DC. Encoder supply: 24 V with short-circuit protection and maximum output current of 20 mA; maximum 50 mA per channel for a duration < 10 s.
- BaseUnit and mounting variant: Suitable for BU type A0, A1 with 2-wire and 4-wire connections. Mechanical coding element: Type A.
- Protection and lifecycle: Conformal coating is provided. Product lifecycle: Active Product. Horizontal installation supports -40 °C to 70 °C, with +85 °C for 10 min under OT4, ST1/ST2 according to EN 50155.
Technical Summary
| Product type designation | AI 4xI 2-/4-wire ST |
|---|---|
| Product lifecycle | Active Product |
| Supply voltage, rated value (DC) | 24 V |
| Permissible supply voltage range (DC) | 19.2 V to 28.8 V |
| Number of analog inputs | 4; > 60 °C max. 1x ±20 mA permissible |
| Input ranges (rated values), currents | 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Resolution with overrange (bit including sign), max. | 16 bit |
| Usable BaseUnits | BU type A0, A1 |
| Firmware update possible | Yes |
| Horizontal ambient temperature during operation | -40 °C to 70 °C; +85 °C for 10 min (OT4, ST1/ST2 according to EN 50155) |
Frequently Asked Questions
What exact Siemens order number should be confirmed for this module?
Confirm order number 6AG2134-6GD01-4BA1 and product type designation AI 4xI 2-/4-wire ST.
Which BaseUnits and connection variants are supported?
It supports BU type A0, A1 for both 2-wire and 4-wire connections.
What supply voltage and input capacity should be checked?
The rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC. The module has 4 analog inputs; above 60 °C, maximum 1x ±20 mA is permissible.
Can the firmware be updated?
Yes. Firmware update is possible.