Key Features
- Product identity: SIPLUS ET 200SP DI 16x24VDC ST digital input module, based on 6ES7131-6BH01-0BA0.
- Digital inputs: 16 parameterizable digital inputs with P-reading sourcing/sinking input and an IEC 61131 type 3 input characteristic.
- Supply voltage: Rated supply voltage: 24 V DC; permissible range: 19.2 V to 28.8 V DC. Reverse polarity protection: Yes.
- BaseUnit and connections: Usable BaseUnit: BU type A0. A 1-wire connection uses BU type A0; 2-wire, 3-wire, and 4-wire connections require BU type A0 + Potential distributor module.
- Diagnostics: Module diagnostics include wire break, supply voltage monitoring, diagnostic alarm, readable diagnostic information, and group error. Short-circuit diagnostics: No.
- Conformal coating and lifecycle: Conformal coating with -40…+70 °C and OT4 with ST1/2 (+85 °C for 10 minutes). Lifecycle: Active Product.
Technical Summary
| Product type designation | DI 16x24VDC ST |
|---|---|
| Digital inputs | 16; parameterizable: Yes |
| Rated input voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Usable BaseUnits | BU type A0 |
| Input characteristic | IEC 61131, type 3 |
| Input delay | 0.05 ms to 20 ms, each case + delay of 30 to 500 μs depending on line length |
| Firmware update possible | No |
| Conformal coating | -40…+70 °C; OT4 with ST1/2 (+85 °C for 10 minutes) |
| Product lifecycle | Active Product |
Frequently Asked Questions
What order number should be confirmed for this Siemens module?
Confirm the complete order number 6AG2131-6BH01-4BA0.
What input and supply voltage does the module have?
The rated supply and input voltage is 24 V DC. The permissible supply voltage range is 19.2 V to 28.8 V DC.
Which BaseUnit and connection configuration are supported?
BU type A0 is supported. A 1-wire connection uses BU type A0; 2-wire, 3-wire, and 4-wire connections require BU type A0 + Potential distributor module.
What firmware and diagnostics details should be checked?
FW update possible: No. Diagnostics include wire break, supply voltage monitoring, diagnostic alarm, readable diagnostic information, and group error; short-circuit diagnostics are not available.