Product Description
Key Features
- Fail-safe analog inputs: 4 analog inputs for current measurement, with fail-safe operation up to PLe according to ISO 13849-1 and SIL 3 according to IEC 61508.
- Current input ranges: Supports 0 to 20 mA and 4 mA to 20 mA input ranges, with 125 Ω input resistance for each range.
- 2-wire and 4-wire connections: Supports current measurement with 2-wire and 4-wire transducers; 2-wire transmitter burden is max. 650 Ω.
- Supply and encoder output: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V. Encoder supply provides 24 V and max. 300 mA total current of all encoders/channels.
- Signal diagnostics: Diagnostics include supply-voltage monitoring, wire-break and short-circuit detection, diagnostic alarms, and green/red LED indications.
- SIPLUS protection and dimensions: Has conformal coating, horizontal installation temperature of -30 °C to 60 °C, and dimensions of 15 mm × 73 mm × 58 mm.
Applications
- Current measurement: Measures current signals through 2-wire and 4-wire transducers using the 0 to 20 mA and 4 mA to 20 mA input ranges.
Technical Summary
| Product type designation | F-AI 4xI 0(4)..20mA 2-/4-wire HF |
|---|---|
| Product lifecycle | Active Product |
| Number of analog inputs | 4 |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Input ranges | 0 to 20 mA; 4 mA to 20 mA |
| Resolution with overrange, max. | 16 bit |
| Connection of signal encoders | 2-wire and 4-wire transducers |
| Performance level | PLe according to ISO 13849-1 |
| Safety integrity level | SIL 3 according to IEC 61508 |
| Horizontal installation temperature | -30 °C to 60 °C |
Frequently Asked Questions
What exact order number should be checked for this module?
The exact order number is 6AG1136-6AA00-2CA1.
Which input configuration does the module have?
It has 4 analog current inputs for 2-wire and 4-wire transducers, supporting 0 to 20 mA and 4 mA to 20 mA.
What supply voltage should be confirmed?
Confirm a rated supply voltage of 24 V DC and a permissible range of 19.2 V to 28.8 V DC.
Which firmware and engineering details should be checked?
FW update is possible, and the module is configurable/integrated with STEP 7 TIA Portal from version see entry ID: 109746275.
What lifecycle information is supplied for this exact item?
The supplied lifecycle status is Active Product.