Product Description
Key Features
- Exact product identity: SIPLUS ET 200SP AQ 2xU/I HS analog output module, based on 6ES7135-6HB00-0DA1; Firmware version V2.0.
- Analog output capacity: 2 analog outputs with voltage and current output ranges, including 0 to 10 V, 4 mA to 20 mA, and -20 mA to +20 mA.
- Resolution and oversampling: Up to 16 bit resolution; analog output with oversampling supports 2 channels per module.
- Supply and diagnostics: 24 V rated DC supply with 19.2 V to 28.8 V permissible range, reverse polarity protection, channel diagnostics, and diagnostic alarm.
- BaseUnit and coding: Suitable for BU type A0, A1; mechanical coding element Type A and color code CC00.
- Conformal coating and temperature: Conformal coating with -40…+60 °C ambient temperature during horizontal operation; vertical operation is specified to 50 °C maximum.
Technical Summary
| Product type designation | AQ 2xU/I HS |
|---|---|
| Firmware version | V2.0 |
| Analog outputs | 2 |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Resolution | 16 bit |
| Oversampling | Yes; 2 channels per module |
| Output ranges | 0 to 10 V; 1 V to 5 V; -5 V to +5 V; -10 V to +10 V; 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Usable BaseUnits | BU type A0, A1 |
| Channel diagnostics | Yes |
| Operating temperature | -40…+60 °C horizontal; -40…+50 °C vertical |
| Product lifecycle | Active Product |
Frequently Asked Questions
What order number should be confirmed for this Siemens analog output module?
Confirm the complete order number 6AG1135-6HB00-2DA1 and the product type designation AQ 2xU/I HS.
Which output configuration does 6AG1135-6HB00-2DA1 provide?
It provides 2 analog outputs with voltage and current ranges, including 0 to 10 V, 1 V to 5 V, 4 mA to 20 mA, and -20 mA to +20 mA.
Which firmware version is supplied for this module?
Firmware version V2.0.
Which BaseUnits and mounting orientation are specified?
It is suitable for BU type A0, A1. Ambient temperature is -40…+60 °C for horizontal installation and -40…+50 °C for vertical installation.