Product Description
Key Features
- Analog input configuration: AI 2xU/I 2-/4-wire HF with 2 differential analog inputs for voltage measurement and 2 for current measurement.
- Resolution and ranges: Resolution with overrange is up to 16 bit. Supported ranges include 0 to +10 V, 1 V to 5 V, -10 V to +10 V, -5 V to +5 V, 0 to 20 mA, -20 mA to +20 mA and 4 mA to 20 mA.
- Supply and protection: Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection.
- Diagnostics and firmware: The module has channel diagnostics, diagnostic and limit value alarms, a V1.0 firmware version, and firmware updates are possible.
- Installation and dimensions: It is suitable for BU type A0 and A1, with automatic encoding and a Type A mechanical coding element. Dimensions are 15 mm wide, 73 mm high and 58 mm deep; weight is approximately 32 g.
Applications
- Voltage measurement: The module supports voltage measurement through its analog inputs.
- Current measurement: The module supports current measurement with 2-wire and 4-wire transducers.
Technical Summary
| Product type | AI 2xU/I 2-/4-wire HF |
|---|---|
| Based on | 6ES7134-6HB00-0CA1 |
| Analog inputs | 2; Differential inputs |
| Resolution with overrange | 16 bit |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Firmware version | V1.0 |
| Usable BaseUnits | BU type A0, A1 |
| Input ranges | 0 to +10 V; 1 V to 5 V; -10 V to +10 V; -5 V to +5 V; 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Operating temperature | -40 °C to 60 °C horizontal installation; -40 °C to 50 °C vertical installation |
| Lifecycle | Active Product |
Frequently Asked Questions
What order number should be checked for this Siemens analog input module?
Check the complete order number 6AG1134-6HB00-2CA1 and the supplied base product 6ES7134-6HB00-0CA1.
Which BaseUnits are supported?
The module is suitable for BU type A0 and A1 for both 2-wire and 4-wire connections.
What firmware information is supplied?
The firmware version is V1.0, and firmware updates are possible.
What configuration details should be confirmed before a request?
Confirm the required voltage or current input range, 2-wire or 4-wire transducer connection, quantity, destination and condition preference.