Product Description
Key Features
- Product identity: SIPLUS ET 200S EM 2 AE I HF based on 6ES7134-4MB02-0AB0, with conformal coating and 15 mm overall width.
- Analog inputs: Has 2 analog inputs supporting rated current ranges of -20 mA to +20 mA and 4 mA to 20 mA.
- Resolution and cycle time: Provides 15 bit+sign for -20 mA to +20 mA and 15 bit for 4 mA to 20 mA; cycle time is 0.5 ms for 2 channels without noise suppression.
- Supply and protection: Load voltage L+ is 24 V DC rated value; reverse polarity protection and short-circuit-proof transmitter power supply are present.
- Diagnostics: Has wire-break diagnosis for the 4 mA to 20 mA measuring range, group error diagnosis, overflow/underflow diagnosis, and a red group error SF LED.
- Lifecycle data: Product lifecycle: Product cancellation.
Applications
- Current measurement: Supports current measurement as a 2-wire transducer, with a maximum transmitter burden of 750 Ω.
- Analog signal diagnostics: Supports wire-break, group error, and overflow/underflow diagnostics for the analog inputs.
Technical Summary
| Order number | 6AG1134-4MB02-2AB0 |
|---|---|
| Product family | SIPLUS ET 200S EM 2 AE I HF |
| Base module | 6ES7134-4MB02-0AB0 |
| Analog inputs | 2 |
| Rated input ranges | -20 mA to +20 mA; 4 mA to 20 mA |
| Resolution | 15 bit+sign; 15 bit |
| Cycle time | 0.5 ms for 2 channels without noise suppression |
| Load voltage L+ | 24 V DC rated value |
| Protection coating | Conformal coating |
| Lifecycle | Product cancellation |
Frequently Asked Questions
What order number should be confirmed for this Siemens module?
Confirm order number 6AG1134-4MB02-2AB0 and the base module 6ES7134-4MB02-0AB0.
How many analog inputs does the module have?
It has 2 analog inputs.
Which current input ranges are supported?
The rated input ranges are -20 mA to +20 mA and 4 mA to 20 mA.
What diagnostics are available?
It has wire-break diagnosis for the 4 mA to 20 mA measuring range, group error diagnosis, and overflow/underflow diagnosis.
What lifecycle data should be checked?
The supplied lifecycle data is Product cancellation; confirm the required quantity, destination, and condition preference in the inquiry.