Product Description
Key Features
- Digital output configuration: 4 parameterizable Triac digital outputs with current-sourcing operation; current-sinking operation is not supported.
- Output capacity: Rated output current is 2 A per channel and maximum module current is 8 A. With resistive load, maximum switching capacity is 2 A, or 4 A as described in the manual.
- Supply and output voltage: Rated AC supply voltage is 230 V at 47 … 63 Hz. Rated AC output voltage is 230 V, with a stated range of 24V AC to 230V AC.
- Diagnostics and status: Channel-by-channel open-circuit detection and wire-break diagnosis are available, with group error, supply-voltage monitoring, diagnostic alarms, and green/red status LEDs.
- Installation and identification: Suitable for BU type U0 with color code CC20 and type C mechanical coding element. The module has conformal coating and a collected temperature range of -40…+70 °C.
Technical Summary
| Product type | DQ 4×24 … 230 V AC/2 A HF |
|---|---|
| Product lifecycle | Active Product |
| Digital outputs | 4; Triac; parameterizable; current-sourcing |
| Rated supply voltage | 230 V AC; 47 … 63 Hz |
| Rated output voltage | 230 V AC; 24V AC to 230V AC |
| Rated output current | 2 A per channel |
| Maximum module current | 8 A |
| BaseUnit | BU type U0 |
| Firmware update | Yes |
| Color code | CC20 |
| Diagnostics | Open-circuit detection and wire-break diagnosis channel by channel; group error |
| Conformal coating | -40…+70 °C |
Frequently Asked Questions
What order number should be confirmed for this Siemens module?
Confirm 6AG1132-6FD00-7CU0 on the nameplate; the module is based on 6ES7132-6FD00-0CU0.
How many digital outputs does the module have?
It has 4 Triac digital outputs, and the outputs are parameterizable and current-sourcing.
Which BaseUnit is supported?
BU type U0 is supported for 1-wire, 2-wire, and 3-wire connection variants; the 3-wire variant uses BU type U0 plus a Potential distributor module.
Does the module provide short-circuit protection?
No. External fusing is necessary, and the module supply requires a miniature fuse with 10 tripping current and a quick-response tripping characteristic.