Product Description
Key Features
- Digital output identity: Product type designation: DQ 4×24 V DC/2 A ST, with 4 source outputs (PNP, current-sourcing).
- Supply and output rating: Rated supply voltage: 24 V DC, with a permissible range of 19.2 V to 28.8 V. Output current for signal "1": 2 A rated value.
- Output protection and diagnostics: The outputs have short-circuit protection, channel diagnostics, and monitoring for supply voltage, wire break, short-circuit, and group error.
- Configuration and mounting: Based on 6ES7132-6BD20-0BA0 and suitable for BU type A0. STEP 7 TIA Portal is configurable/integrated from the version associated with entry ID: 109746275.
- Conformal coating and lifecycle: The module has conformal coating and a -40…+70 °C specification. Product lifecycle: Start of final year of support.
Technical Summary
| Product type | DQ 4×24 V DC/2 A ST |
|---|---|
| Based on | 6ES7132-6BD20-0BA0 |
| Usable BaseUnits | BU type A0 |
| Digital outputs | 4; > +60 °C number of simultaneously controllable outputs max. 2x 0.25 A or max. 4x 0.125 A, max. total current 0.5 A |
| Output type | Source output (PNP, current-sourcing) |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Output current for signal "1" | 2 A rated value |
| Short-circuit protection | Yes |
| Address space per module, max. | 32 byte |
| Power loss, typ. | 1 W |
| Product lifecycle | Start of final year of support |
Frequently Asked Questions
What order number should be confirmed for this digital output module?
Confirm Siemens 6AG1132-6BD20-7BA0 and the product type designation DQ 4×24 V DC/2 A ST. The module is based on 6ES7132-6BD20-0BA0.
What supply voltage and output rating does it use?
Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC. The output current for signal "1" is 2 A rated value.
Which BaseUnit is suitable for this module?
It is suitable for BU type A0.
What diagnostics are provided?
Diagnostics include monitoring the supply voltage, wire break, short-circuit, and group error. The outputs also have short-circuit protection.
What lifecycle information should be checked?
The product lifecycle is Start of final year of support. Confirm the required quantity, destination, and condition preference when submitting a legacy-part inquiry.