Product Description
Key Features
- Exact product identity: SIPLUS LOGO! 12/24RCEO based on 6ED1052-2MD08-0BA1, with conformal coating.
- Power supply and I/O: 12/24 V DC/relay power supply and I/O; 8 digital inputs, of which 4 can be used in analog mode from 0 to 10 V, and 4 relay digital outputs.
- Interfaces and functions: Ethernet, integrated web server, data log, user-defined web pages, modularly expandable, and standard microSD card for LOGO! Soft Comfort V8.3 or higher.
- Mounting and display: Mounting on 35 mm DIN rail, 4 spacing units wide; without display.
- Environmental range: Ambient temperature during operation: -40 °C to 70 °C; cold restart from -25 °C, with condensation or frost permitted, but no commissioning under condensation conditions.
- Lifecycle and dimensions: Product lifecycle: Start of final year of support. Dimensions: 71.5 mm width, 90 mm height, 60 mm depth; net weight 0.250 kg.
Technical Summary
| Product model | 6AG1052-2MD08-7BA1 |
|---|---|
| Base model | 6ED1052-2MD08-0BA1 |
| Power supply and I/O | 12/24 V DC/relay |
| Digital inputs | 8; of which 4 can be used in analog mode (0 to 10 V) |
| Digital outputs | 4; relays |
| Interfaces | Ethernet; integrated web server |
| Mounting | 35 mm DIN rail, 4 spacing units wide |
| Operating temperature | -40 °C to 70 °C; Tmax > +55 °C: max. load 1 A per relay or max. load 3 A per relay and half the number of DIs (no adjacent points) |
| Cold restart | -25 °C; condensation/frost permitted, no commissioning under condensation conditions |
| Conformal coating | Class 2 for high reliability; Type 1 protection |
| Product lifecycle | Start of final year of support |
Frequently Asked Questions
What is the exact model and base model?
The exact model is 6AG1052-2MD08-7BA1, based on 6ED1052-2MD08-0BA1.
What power supply and I/O configuration does it have?
It has 12/24 V DC/relay power supply and I/O, 8 digital inputs, of which 4 can be used in analog mode from 0 to 10 V, and 4 relay digital outputs.
How is the module mounted?
It mounts on a 35 mm DIN rail and is 4 spacing units wide.
What environmental temperature limits apply?
The operating range is -40 °C to 70 °C. At temperatures above +55 °C, the maximum load is 1 A per relay or 3 A per relay with half the number of DIs and no adjacent points.
What should be confirmed for a legacy-part inquiry?
Confirm the exact order number, installed configuration, required quantity, destination, condition preference, and requested date.