Product Description
Key Features
- Analog output capacity: 4 analog output channels with 16-bit resolution and 0.1% accuracy.
- Output ranges: Supported ranges include 0 to 10 V, 1 V to 5 V, -10 V to +10 V, 0 to 20 mA, -20 mA to +20 mA and 4 mA to 20 mA.
- Interfaces and connections: Voltage outputs support two-wire and four-wire connections; current outputs support two-wire connections. The front connector with screw terminals or push-in must be ordered separately.
- Diagnostics and operating functions: The module has diagnostics, diagnostic alarms, substitute values, isochronous mode, MSO and supply-voltage monitoring.
- Safety-oriented shutdown: Supports safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015.
Applications
- Safety-oriented load-group shutdown: Supports the safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015.
- Output diagnostics: Provides supply-voltage monitoring, wire-break diagnosis for current outputs and short-circuit diagnosis for voltage outputs.
Technical Summary
| Product type | AQ 4xU/I HF |
|---|---|
| Analog outputs | 4 |
| Resolution | 16 bit |
| Accuracy | 0.1% |
| Rated supply voltage | 24 V |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Firmware version | V1.1.0 |
| Product lifecycle | Active Product |
Frequently Asked Questions
What order number should be confirmed for this analog output module?
Confirm 6ES7532-5ND00-0AB0 on the nameplate or installed-part documentation.
Which firmware version does 6ES7532-5ND00-0AB0 have?
Firmware version: V1.1.0. Firmware update is possible.
Which connector is included with the module?
The front connector with screw terminals or push-in is not included and must be ordered separately. Delivery includes the infeed element, shielding bracket and shield terminal.
What supply voltage does the module use?
Rated supply voltage: 24 V DC. The permissible range is 19.2 V to 28.8 V DC.
Which output diagnostics are available?
Wire-break diagnosis is available only for output type current, and short-circuit diagnosis is available only for output type voltage. Supply-voltage monitoring and diagnostic alarms are also available.