Product Description
Key Features
- Digital I/O configuration: SM 1223, DI 16×24 V DC, DQ 16×24 V DC, with 16 digital inputs and 16 digital outputs.
- 24 V DC supply: Rated supply voltage is 24 V DC, with a permissible range of 20.4 V to 28.8 V.
- Transistor output capacity: Outputs have a switching capacity of 0.5 A maximum with resistive load and 5 W maximum on lamp load.
- Input signal thresholds: Input voltage is 5 V DC at 1 mA for signal "0" and 15 V DC at 2.5 mA for signal "1".
- Installation-dependent capacity: The module supports 16 in all mounting positions up to 40 °C and 8 A current per mass for horizontal installation up to 50 °C.
- Protection and diagnostics: The module has IP20 protection, diagnostic alarms, and status LEDs for inputs and outputs; output short-circuit protection must be provided externally.
Technical Summary
| Product type | SM 1223, DI 16×24 V DC, DQ 16×24 V DC |
|---|---|
| Digital inputs | 16; in groups of 2 |
| Digital outputs | 16; in groups of 1 |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 20.4 V to 28.8 V DC |
| Output type | Transistor; 0.5 A rated value for signal "1" |
| Input signal thresholds | Signal "0": 5 V DC at 1 mA; signal "1": 15 V DC at 2.5 mA |
| Input parameterization | 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four |
| Potential separation | Digital inputs in groups of 2; digital outputs in groups of 1; outputs to backplane bus: 500 V AC |
| Protection | IP20 |
Frequently Asked Questions
Which order number should be confirmed for this Siemens digital I/O module?
Confirm the complete order number 6ES7223-1BL32-0XB0 on the installed part or nameplate.
What I/O configuration does 6ES7223-1BL32-0XB0 have?
It has 16 digital inputs and 16 digital outputs. Inputs are grouped in 2, and outputs are grouped in 1.
What supply voltage does this module use?
The rated supply voltage is 24 V DC, with a permissible range of 20.4 V to 28.8 V DC.
Does the module include output short-circuit protection?
No. Output short-circuit protection must be provided externally.
What should be confirmed for a legacy-part inquiry?
Confirm the exact order number, installed I/O configuration, quantity, destination, requested date, and preferred condition.