Product Description
Key Features
- Serial communication interfaces: RS-422, RS-485 and RS-232 interfaces with a Push-in terminal connection.
- Communication protocols: Supports Freeport, 3964 (R), USS and MODBUS RTU master and device modes.
- Transmission rate: Maximum transmission rate is 250 Kbit/s for RS-485 and 115.2 kbit/s for RS-232 and RS-422.
- Supply and current consumption: Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC. Rated current consumption is 31 mA and maximum current consumption is 35 mA.
- Firmware and BaseUnit: Firmware update is possible, and the module is usable with BU type A0.
- Product lifecycle: Lifecycle status: Active Product.
Applications
- Serial device communication: Provides serial communication through RS-422, RS-485 and RS-232 using Freeport, 3964 (R), USS and MODBUS RTU.
Technical Summary
| Product type | CM PtP |
|---|---|
| Interfaces | RS-422, RS-485, RS-232 |
| Connection | Push-in terminal |
| Maximum RS-485 transmission rate | 250 kbit/s |
| Maximum RS-232 and RS-422 transmission rate | 115.2 kbit/s |
| Supply voltage | 24 V DC; permissible range 19.2 V to 28.8 V DC |
| Current consumption | 31 mA rated; 35 mA maximum |
| Usable BaseUnits | BU type A0 |
| Firmware update | Yes |
| Lifecycle | Active Product |
Frequently Asked Questions
What order number should be confirmed for this CM PtP module?
Confirm the complete order number 6ES7137-6AA01-0BA0 on the nameplate or installed-part record.
Which serial interfaces are included?
The module has RS-422, RS-485 and RS-232 interfaces with a Push-in terminal connection.
Which BaseUnit is specified for this module?
The module is usable with BU type A0.
What firmware information should be checked?
Firmware update is possible; confirm the installed firmware version when matching the configuration.