Product Description
Key Features
- Energy measurement functions: Measures voltage, current, energy, frequency, power, active power, reactive power and power factor.
- Voltage and current inputs: Voltage measurement supports 277 V between phase and neutral conductor and 480 V between line conductors. Current measurement supports 1% to 100% relative current, relative to the secondary rated current 5 A.
- Installation and supply: Suitable for BU type D0; supply is via voltage measurement channel L1. Rated supply is AC 100 – 277 V, with a permissible range of 90 V to 293 V.
- Measured value access: Provides cyclic and acyclic measured value access, fixed and freely definable measured value sets, and a typical 50 ms cycle time for all channels.
- Interfaces and configuration: Supports STEP 7 TIA Portal from V13 SP1, STEP 7 V5.5 SP4 and higher, PROFIBUS GSD Revision 5 and PROFINET GSD V2.3.
- Diagnostics and lifecycle: Includes diagnostic alarms, limit value alarms, hardware interrupts, PWR-LED, channel status display, channel diagnostics and module diagnostics. Firmware version is V4.0; product lifecycle is Product cancellation.
Applications
- Voltage measurement: Measures voltage with or without a voltage transformer.
- Current measurement: Measures current with a current transformer.
- Energy measurement: Measures energy, frequency, power, active power, reactive power and power factor.
Technical Summary
| Product type | AI Energy Meter 480VAC ST |
|---|---|
| Firmware version | V4.0 |
| Usable BaseUnit | BU type D0 |
| Supply voltage | AC 100 – 277 V; permissible range 90 V to 293 V |
| Line frequency | 47 Hz to 63 Hz |
| Measured value access | Cyclic and acyclic; fixed and freely definable measured value sets |
| Voltage measurement | 277 V phase to neutral; 480 V between line conductors |
| Current measurement | 1% to 100% relative current; secondary rated current 5 A |
| Cycle time, all channels | 50 ms |
| Product lifecycle | Product cancellation |
Frequently Asked Questions
What is the exact order number and product type?
The order number is 6ES7134-6PA20-0BD0 and the product type is AI Energy Meter 480VAC ST.
Which BaseUnit is suitable for this module?
It is suitable for BU type D0; the 2-wire connection selection also lists BU20-P12+A0+0B.
What supply voltage does the module use?
Supply is via voltage measurement channel L1. The rated supply is AC 100 – 277 V, with a permissible range of 90 V to 293 V.
Which firmware and engineering versions are supplied?
Firmware version is V4.0. STEP 7 TIA Portal is configurable/integrated from V13 SP1, and STEP 7 from V5.5 SP4 and higher.