Product Description
Key Features
- Product identity: SIMATIC ET 200SP analog input module with product type designation AI Energy Meter CT HF.
- Current transformer input: Supports current measurement with a 1 A or 5 A current transformer; maximum 4 current measurements.
- Measurement functions: Measures voltage, current, energy, frequency, power, active power, reactive power, power factor, harmonics, THD, voltage dip, and voltage swell.
- Line analysis: Provides line analysis with monitoring of instantaneous and half-wave values, plus THD measurement and harmonics for current and voltage.
- Supply and BaseUnit: Rated supply voltage is 24 V DC, with a permissible range from 19.2 V to 28.8 V DC. Usable BaseUnit: BU type U0.
- Firmware and diagnostics: Firmware version V8.0; FW update possible. Diagnostic alarm, limit value alarm, hardware interrupt, and channel diagnostics are available.
Applications
- Electrical measurement: Measures voltage, current, energy, frequency, power, active energy, reactive energy, and power factor.
- Line analysis: Performs line analysis, including THD measurement, harmonics, voltage dip, and voltage swell detection.
Technical Summary
| Product type | AI Energy Meter CT HF |
|---|---|
| Firmware version | V8.0 |
| Current transformer input | 1 A or 5 A current transformer; maximum 4 current measurements |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Usable BaseUnit | BU type U0 |
| Supported power supply systems | TT, TN, IT |
| Communication engineering | STEP 7 V16 or higher with HSP; V5.5 SP3 or higher; PROFIBUS GSD Revision 3 and 5 and higher; PROFINET GSD V2.3 |
| Cycle time, all channels | 50 ms; time for consistent update of all measured and calculated values |
| Sampling frequency, max. | 2 048 kHz |
| Mounting position | any |
Frequently Asked Questions
What is the exact order number and product type?
The exact order number is 6ES7134-6PA01-0CU0, and the product type designation is AI Energy Meter CT HF.
Which current transformer inputs should be confirmed?
Confirm whether the installed configuration uses a 1 A or 5 A current transformer; current measurement is available for up to 4 measurements.
Which firmware version does this module have?
Firmware version is V8.0, and FW update is possible.
Which BaseUnit is usable for this module?
The usable BaseUnit is BU type U0.