Product Description
Key Features
- Product identity: AI energy meter 400VAC ST for SIMATIC ET 200SP; usable BaseUnit: BU type D0.
- Measurement functions: Measures voltage, current, energy, frequency, power, active power and reactive power.
- Supply and voltage inputs: Supply via voltage measurement channel L1; rated supply value: 100 – 240 V AC, permissible range: 90 V to 264 V AC.
- Interfaces and engineering: PROFIBUS from GSD Revision 5 and PROFINET from GSD version V2.3; STEP 7 TIA Portal configurable/integrated from V13 SP1.
- Installation and diagnostics: Any mounting position; diagnostic alarm, supply-voltage monitoring, green channel-status LED, red Fn LED and green/red DIAG LED.
- Lifecycle and physical data: Product cancellation; width 20 mm, height 73 mm, depth 58 mm, weight approx. 45 g. The order description identifies a spare part.
Applications
- Voltage measurement: Measures line voltage between phase and neutral conductor and between line conductors.
- Current and energy measurement: Measures current, active energy and reactive energy.
- Power and frequency measurement: Measures active power, reactive power, power factor and frequency.
Technical Summary
| Product type | AI energy meter 400VAC ST |
|---|---|
| Firmware version | V3.0 |
| Usable BaseUnit | BU type D0 |
| Supply voltage | 100 – 240 V AC; permissible range 90 V to 264 V AC |
| Voltage measurement | 230 V phase-to-neutral; 400 V line-to-line |
| Current measurement | 5 % to 100 % of secondary rated current; 1 A, 5 A |
| Cycle time | 50 ms; consistent update of all measured and calculated values |
| Engineering and communication | STEP 7 TIA Portal V13 SP1; STEP 7 V5.5 SP4 and higher; PROFIBUS GSD Revision 5; PROFINET V2.3 |
| Measurement procedure | TRMS for voltage and current; seamless measured-value acquisition |
| Mounting position | any |
| Product lifecycle | Product cancellation |
Frequently Asked Questions
What order number should be confirmed for this AI energy meter?
Confirm 6ES7134-6PA01-0BD0 on the nameplate or installed-part documentation.
Which BaseUnit is usable with this module?
The usable BaseUnit is BU type D0.
Which firmware version does the module have?
The firmware version is V3.0.
What voltage range does it measure?
It measures 230 V between phase and neutral conductor and 400 V between line conductors; the stated permissible supply range is 90 V to 264 V AC.