Product Description
Key Features
- Exact product identity: SIMATIC ET 200SP analog input module, product type designation AI 4xTC HS, color code CC00.
- Thermocouple inputs: 4 analog inputs support thermocouple types B, C, E, J, K, L, N, R, S, T, U, and TXK/TXK(L) to GOST.
- Input resolution and ranges: Resolution is 16 bit including sign; voltage input ranges include -1 V to +1 V, -250 mV to +250 mV, -50 mV to +50 mV, and -80 mV to +80 mV.
- Supply and diagnostics: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V, reverse polarity protection, channel diagnostics, wire-break detection, and overflow/underflow detection channel by channel.
- BaseUnit and installation: Suitable BaseUnits are BU type A0 and A1; 2-wire connection is supported, with shielded cable up to 200 m, or 100 m for thermocouples.
- Engineering and firmware: FW update is possible. STEP 7 TIA Portal is configurable from V15 with HSP 265 or integrated as of V15.1; STEP 7 is configurable from V5.5 SP3 or higher.
Applications
- Thermocouple temperature measurement: Measures temperature using supported thermocouple types with an adjustable temperature unit of °C/°F/K.
Technical Summary
| Product type designation | AI 4xTC HS |
|---|---|
| Analog inputs | 4 |
| Resolution | 16 bit including sign |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Supported BaseUnits | BU type A0, A1 |
| Input cycle time | 5 ms minimum, all channels |
| Firmware update | Yes |
| Product lifecycle | Active Product |
Frequently Asked Questions
What order number identifies this Siemens module?
The exact order number is 6ES7134-6JD00-0DA1, with product type designation AI 4xTC HS.
How many analog inputs does it have?
It has 4 analog inputs and supports thermocouple types B, C, E, J, K, L, N, R, S, T, U, and TXK/TXK(L) to GOST.
Which BaseUnits and connection are supported?
It is suitable for BU type A0 and A1 and supports 2-wire connection.
What firmware and engineering versions should be confirmed?
FW update is possible. Confirm whether the installation uses STEP 7 TIA Portal V15 with HSP 265 or V15.1 integration, or STEP 7 V5.5 SP3 or higher.