Product Description
Key Features
- Digital output identity: DQ 4×24 … 230 V AC/2 A HF digital output module with 4 Triac outputs and current-sourcing operation.
- Operating modes: Supports DQ, DQ with energy-saving function, phase control from 8.5 … 100% of the phase angle, half-wave, and full-wave operation.
- Output capacity: Rated output current is 2 A per channel; maximum current is 8 A per module. With resistive load, maximum switching capacity is 2 A; maximum 4 A is noted in the manual.
- BaseUnit and coding: Fits BU type U0 for 1-wire and 2-wire connections; 3-wire connection uses BU type U0 plus a potential distributor module. Mechanical coding element: type C.
- Diagnostics and firmware: Provides channel-by-channel open-circuit detection and wire-break diagnosis, group error indication, I&M0 to I&M3 data, and firmware updates. HW functional status: From FS03.
Applications
- Digital output switching: Controls digital outputs in DQ mode, including DQ with energy-saving function.
- Phase control: Performs phase control within the 8.5 … 100% control area of the phase angle.
- Output diagnostics: Provides channel-by-channel open-circuit detection and wire-break diagnosis.
Technical Summary
| Product model | 6ES7132-6FD00-0CU0 |
|---|---|
| Product type | DQ 4×24 … 230 V AC/2 A HF |
| Output type and count | Triac; 4 digital outputs |
| Rated output voltage | 230 V; 24V AC to 230V AC |
| Rated output current | 2 A per channel |
| Maximum current per module | 8 A |
| BaseUnit | BU type U0 |
| Supported engineering | STEP 7 TIA Portal from V14; STEP 7 V5.5 or higher; PROFINET GSDML V2.3; PROFIBUS GSD as of Revision 5 |
| Firmware update | Yes |
| Lifecycle status | Active Product |
| Protection and diagnosis | No short-circuit protection; external fusing necessary; channel-by-channel open-circuit detection |
Frequently Asked Questions
What order number should be confirmed for this digital output module?
Confirm the complete nameplate order number: 6ES7132-6FD00-0CU0.
Which BaseUnit and connection variants does the module use?
It uses BU type U0 for 1-wire and 2-wire connections. A 3-wire connection uses BU type U0 plus a potential distributor module.
What firmware and engineering versions should be checked?
Firmware updates are possible. STEP 7 TIA Portal is configurable/integrated from V14, and STEP 7 is configurable/integrated from STEP 7 V5.5 or higher.
Does the module include short-circuit protection?
It is without short-circuit protection; external fusing is necessary. Overload protection is also not provided, and a miniature fuse must be provided in the module supply.