Product Description
Key Features
- Product identity and lifecycle: SIMATIC DP, ET 200eco PN, 4 AO U/I; 4xM12; IP67. Product cancellation.
- Analog output capacity: 4 analog outputs support voltage ranges 0 to 10 V, 1 V to 5 V and -10 V to +10 V, plus current ranges 0 to 20 mA, -20 mA to +20 mA and 4 mA to 20 mA.
- Supply and protection: Rated supply is 24 V DC with reverse polarity protection and NEC Class 2 power supply required. Short-circuit protection is electronic at 1.4 A.
- PROFINET interface: 1 PROFINET interface with M12 port, integrated switch and transmission rate up to 100 Mbit/s; PROFINET IO, MRP, SNMP, DCP, LLDP, ping and ARP are supported.
- Installation and dimensions: Electrical connection uses 4/5-pin M12 circular connectors. Dimensions are 60 mm wide, 175 mm high and 49 mm deep; weight is approximately 930 g.
- Protection and hazardous-area classification: IP degree of protection is IP65/67. ATEX gas explosion protection is Zone 2 and ATEX dust explosion protection is Zone 22.
Applications
- Analog signal output: Provides voltage and current analog outputs through the 4 analog output channels.
- PROFINET IO communication: Supports PROFINET IO communication through the M12 PROFINET interface.
- Diagnostic monitoring: Provides diagnostics, diagnostic alarms, readable diagnostic information and supply-voltage monitoring.
Technical Summary
| Order number | 6ES7145-6HD00-0AB0 |
|---|---|
| Product lifecycle | Product cancellation |
| Analog outputs | 4 |
| Rated supply | 24 V DC |
| Output ranges | 0 to 10 V; 1 V to 5 V; -10 V to +10 V; 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| PROFINET interfaces | 1 |
| Transmission rate, max. | 100 Mbit/s |
| Connection | 4/5-pin M12 circular connectors |
| IP degree of protection | IP65/67 |
| Hazardous-area protection | ATEX gas explosion protection, Zone 2; ATEX dust explosion protection, Zone 22 |
Frequently Asked Questions
What order number should be confirmed for this SIMATIC ET 200eco PN part?
Confirm the complete order number 6ES7145-6HD00-0AB0 on the nameplate or installed configuration.
How many analog outputs does 6ES7145-6HD00-0AB0 have?
It has 4 analog outputs supporting the listed voltage and current output ranges.
Which connectors are used?
The electrical connection uses 4/5-pin M12 circular connectors.
What lifecycle information is supplied for this configuration?
The supplied lifecycle information is Product cancellation.