Product Description
Key Features
- Digital I/O configuration: The module has 4 digital inputs, parameterizable as DIQ, and 8 digital outputs: 4 fixed DQ and 4 parameterizable DIQ.
- Output capacity and protection: Outputs are current-sourcing, rated at 0.5 A for signal "1", with electronic short-circuit protection per channel and 2 A maximum current per group.
- 24 V DC supply: Load voltages 1L+ and 2L+ have a rated value of 24 V DC and a permissible range from 20.4 V to 28.8 V.
- Connections and protection: The supplied configuration has 4x M12 connections and IP65/67 degree of protection.
- Firmware and hardware status: The hardware functional status is FS06 and the firmware version is V2.0.x.
- Engineering and diagnostics: I&M0 to I&M3 data is supported. Configuration is available with STEP 7 V13 SP1 or higher, STEP 7 V5.5 SP4 Hotfix 7 or higher, PROFIBUS GSD Revision 5 or later, and PROFINET GSDML V2.3.1.
Technical Summary
| Product identity | 6ES7143-5AF00-0BA0; SIMATIC ET 200AL; DIQ 4+DQ 4x24VDC/0.5A |
|---|---|
| Lifecycle | Active Product |
| Digital inputs | 4; parameterizable as DIQ |
| Digital outputs | 8; 4 DQ fixed, 4 DIQ parameterizable |
| Load voltage | 1L+ and 2L+: 24 V DC rated; 20.4 V to 28.8 V permissible range |
| Output current | 0.5 A rated value for signal "1"; 2 A maximum current per group |
| Connections | 4x M12 |
| Protection | IP65/67 degree of protection |
| Firmware version | V2.0.x |
| HW functional status | FS06 |
| PROFINET engineering | GSDML V2.3.1 |
| PROFIBUS engineering | GSD as of Revision 5 |
Frequently Asked Questions
What order number should be confirmed for this SIMATIC ET 200AL module?
Confirm the complete order number 6ES7143-5AF00-0BA0 against the installed part or nameplate.
Which I/O configuration does 6ES7143-5AF00-0BA0 have?
It has 4 digital inputs, parameterizable as DIQ, and 8 digital outputs: 4 fixed DQ and 4 parameterizable DIQ.
Which firmware and hardware status should be checked?
The supplied values are firmware version V2.0.x and HW functional status FS06.
Which connections and protection details should be verified?
Verify the 4x M12 connections and IP65/67 degree of protection.