Product Description
Key Features
- Exact product identity: Siemens SIMATIC S7-300 analog output SM 332, 6ES7332-5HD01-0AB0, with 4 AO for voltage and current.
- Output ranges: Voltage ranges: 0 to 10 V, 1 V to 5 V, and -10 V to +10 V. Current ranges: 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
- Supply and protection: Load voltage L+: rated value (DC) 24 V, with reverse polarity protection. Voltage output has short-circuit protection.
- Diagnostics: Diagnostics function, substitute values, and diagnostic alarm are parameterizable. Diagnostic information is readable, with a red group error SF LED.
- Connections and installation: Required front connector: 20-pin. Voltage output uses four-wire connection and current output uses two-wire connection. Removal and insertion with the active backplane bus is possible.
- Isolation and dimensions: Analog outputs are isolated from the backplane bus, load voltage L+, and electronics power supply, but not between channels. Dimensions: 40 mm × 125 mm × 117 mm; weight, approx. 220 g.
Technical Summary
| Product lifecycle | Product cancellation |
|---|---|
| Analog outputs | 4 |
| Output types | Voltage and current |
| Load voltage L+ | Rated value (DC) 24 V |
| Voltage output ranges | 0 to 10 V; 1 V to 5 V; -10 V to +10 V |
| Current output ranges | 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Diagnostics | Parameterizable diagnostics function, substitute values, and diagnostic alarm; readable diagnostic information |
| Required front connector | 20-pin |
| Actuator connections | Voltage output: four-wire connection; current output: two-wire connection |
| Isolation | Between channels and backplane bus, load voltage L+, and electronics power supply: Yes; between channels: No |
Frequently Asked Questions
What is the exact order number of this Siemens analog output module?
The exact order number is 6ES7332-5HD01-0AB0.
How many analog outputs and output ranges does it have?
It has 4 analog outputs. Voltage ranges are 0 to 10 V, 1 V to 5 V, and -10 V to +10 V; current ranges are 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
Which front connector is required?
A 20-pin front connector is required.
What diagnostics are available?
Diagnostics function, substitute values, and diagnostic alarm are parameterizable. Diagnostic information is readable, and a red group error SF LED is provided.
What lifecycle information should be confirmed for this part?
The supplied lifecycle information is Product cancellation. Confirm the required quantity, destination, and condition preference when making an inquiry.