Product Description
Key Features
- Product identity: SIMATIC DP PM-E F PROFIsafe power module for ET200S; spare part.
- Load voltage: Rated load voltage L+: 24 V DC; reverse polarity protection: No.
- Digital output: 1 digital relay output with no short-circuit protection; it can control a digital input.
- Switching capacity: Maximum lamp-load switching capacity: 100 W. Maximum switching frequency: 2 Hz with resistive or lamp load, and 0.1 Hz with inductive load to IEC 60947-5-1, DC-13 / AC-15.
- Diagnostics and isolation: Diagnostics function and readable diagnostic information: Yes. Wire-break diagnosis: No; short-circuit and missing-load-voltage diagnostics: Yes. Digital outputs are isolated from the backplane bus, but not between channels or from load voltage L+.
- Dimensions and weight: 30 mm width, 81 mm height, 52 mm depth; approximate weight: 80 g.
Applications
- Switching voltage buses: A grounded setup relay switches the voltage buses P1 and P2; the module can also be used in a PROFINET configuration with IM 151-3 HF.
Technical Summary
| Product type | SIMATIC DP, PM-E F PROFIsafe power module for ET200S |
|---|---|
| Load voltage L+ | 24 V DC rated value |
| Digital outputs | 1; Relays |
| Address space per module | Inputs: 5 byte; Outputs: 5 byte |
| Diagnostics | Diagnostics function: Yes; diagnostic information readable: Yes |
| Safety mode | Highest safety class: 4 acc. to EN 954; Performance level: e according to ISO 13849-1; SIL: With Std-DO: Max. SIL 2, without Std-DO max. SIL 3 depending on configuration |
| PROFINET configuration | Can also be used with IM 151-3 HF |
| Installation | Horizontal: 10 A up to 40 °C, 8 A up to 55 °C, 7 A up to 60 °C; vertical: 8 A up to 40 °C |
| Product lifecycle | Product cancellation |
Frequently Asked Questions
What exact Siemens model should be confirmed for this spare part?
Confirm order number 6ES7138-4CF42-0AB0 and the SIMATIC DP PM-E F PROFIsafe identity.
What load voltage does 6ES7138-4CF42-0AB0 use?
Its rated load voltage L+ is 24 V DC, with no reverse polarity protection.
How many digital outputs does the module have?
It has 1 relay digital output. Short-circuit protection is not provided.
What mounting limits should be checked?
For horizontal installation, the maximum values are 10 A up to 40 °C, 8 A up to 55 °C, and 7 A up to 60 °C. For vertical installation, the maximum is 8 A up to 40 °C.