Product Description
Key Features
- SIMATIC DP ET200S module: Electronics module for ET200S with 2 analog current inputs and 15 mm width.
- Current input ranges: Supports -20 mA to +20 mA and 4 mA to 20 mA input ranges; both have 50 Ohm input resistance.
- Resolution and conversion: Resolution with overrange is 14 bit including sign; 4 mA to 20 mA provides 13 bit. Conversion time is 65 ms per channel.
- 24 V supply: Rated load voltage L+ is 24 V DC from the power module; typical power loss is 0.6 W.
- Diagnostics and isolation: Provides wire-break diagnostics for the 4 mA to 20 mA measuring range, group error and overflow/underflow diagnostics. The channels are not potential-separated from each other, but are separated from the backplane bus.
- Product lifecycle: Product lifecycle: Product cancellation.
Technical Summary
| Product function | SIMATIC DP electronics module for ET200S |
|---|---|
| Analog inputs | 2 |
| Input ranges | -20 mA to +20 mA; 4 mA to 20 mA, 50 Ohm |
| Rated load voltage L+ | 24 V DC; from power module |
| Resolution with overrange | 14 bit including sign; ±20 mA: 14 bit, 4 mA to 20 mA: 13 bit |
| Conversion time | 65 ms per channel; 55 / 65 ms |
| Potential separation | Between channels: No; between channels and backplane bus: Yes |
| Product lifecycle | Product cancellation |
Frequently Asked Questions
What input ranges does Siemens 6ES7134-4GB11-0AB0 support?
It supports -20 mA to +20 mA and 4 mA to 20 mA input ranges, each with 50 Ohm input resistance.
What supply does this ET200S module require?
Its rated load voltage L+ is 24 V DC from the power module.
What are the module dimensions and weight?
The module is 15 mm wide, 81 mm high and 52 mm deep, with an approximate weight of 40 g.
Does the module have channel potential separation?
It is without potential separation between the channels. Potential separation between the channels and the backplane bus is present.
What lifecycle status should be confirmed for this order number?
The supplied lifecycle status is Product cancellation; confirm the required configuration and requested date for the inquiry.