Product Description
Key Features
- SIMATIC DP ET 200S identity: Electronic module with 4 digital inputs, 15 mm width, SF group-fault LED, and a packing unit of 5 units.
- Digital inputs: 4 digital inputs with AC/DC input voltage. The rated value is 24 V; 24 V to 48 V UC at 47 Hz to 63 Hz.
- Input signal ranges: Signal 0: -6 V to +6 V DC or 0 V to 5 V AC. Signal 1: -15 V DC to -57.6 V DC, 15 V DC to 57.6 V DC, or 15 V AC to 48 V AC.
- Diagnostics and isolation: Parameterizable diagnostics, wire-break diagnosis, and a red SF group-error LED are provided. Digital inputs are isolated from the backplane bus but not between channels.
- Physical and lifecycle data: Dimensions are 15 mm width, 81 mm height, and 52 mm depth; approximate weight is 35 g. Product lifecycle: Product cancellation.
Applications
- Isochronous operation: Supports isochronous mode.
- Wire-break diagnosis: Supports wire-break diagnosis for connected 2-wire sensors.
Technical Summary
| Product function | Isochronous mode: Yes |
|---|---|
| Digital inputs | 4 |
| Input voltage | AC/DC; rated value 24 V; 24 V to 48 V UC at 47 Hz to 63 Hz |
| Input signal 0 | -6 to +6 V DC / 0 to 5 V AC |
| Input signal 1 | -15 V DC to -57.6 V DC; 15 V DC to 57.6 V DC; 15 V AC to 48 V AC |
| Input characteristic | IEC 61131, type 1 |
| Diagnostics | Parameterizable; wire break: Yes |
| Digital input isolation | Between channels: No; between channels and backplane bus: Yes |
| Product lifecycle | Product cancellation |
Frequently Asked Questions
What is the exact order number and module identity?
The order number is 6ES7131-4CD02-0AB0. It is a SIMATIC DP ET 200S electronic module with 4 digital inputs and 15 mm width.
What input voltage does the module use?
The input voltage is AC/DC. The rated value is 24 V; 24 V to 48 V UC at 47 Hz to 63 Hz.
Does it support wire-break diagnostics?
Yes. It supports parameterizable diagnostics and wire-break diagnosis. A minimum load current is necessary for wire-break diagnostics with a 2-wire sensor.
How are the digital inputs isolated?
The digital inputs are not isolated between channels. They are isolated between the channels and the backplane bus.
What lifecycle information should be confirmed for sourcing?
The product lifecycle is Product cancellation. Confirm the exact order number, required quantity, destination, and condition preference when submitting an inquiry.