Product Description
Key Features
- Rated current and motor power: At 400 V and 40 °C, rated operational current is 47 A in standard circuit and 81 A in inside-delta circuit; supplied motor power is 22 kW and 45 kW respectively.
- Soft starter functions: Has an integrated bypass contact system, thyristors, intrinsic device protection, motor overload protection, evaluation of thermistor motor protection, external reset, adjustable current limitation, and a motor brake output.
- Operating voltage: Rated operating voltage is 200 … 460 V in both standard circuit and inside-delta circuit, with -15 % relative negative tolerance and 10 % relative positive tolerance.
- Control supply and connections: AC control supply is 230 V at 50 Hz and 60 Hz. Main current circuit uses box terminals; auxiliary and control circuits use spring-loaded terminals.
- Mounting and dimensions: Dimensions are 170 mm width, 192 mm height, and 270 mm depth. Fastening is by screw fixing; mounting is on a vertical surface with the stated rotation and tilt limits.
- Protection and lifecycle: Front protection is IP20 with finger-safe protection for vertical contact from the front. Product lifecycle data states: Start of final year of support.
Applications
- Motor overload protection: Provides motor overload protection.
- Thermistor motor protection: Evaluates thermistor motor protection.
- Motor braking: Provides a motor brake output.
Technical Summary
| Product designation | Soft starter |
|---|---|
| Rated operational current at 40 °C | 47 A |
| Rated operational current in inside-delta circuit at 40 °C | 81 A |
| Motor power at 400 V, standard circuit | 22 kW |
| Motor power at 400 V, inside-delta circuit | 45 kW |
| Rated operating voltage | 200 … 460 V |
| Control supply | 230 V AC at 50 Hz and 60 Hz |
| Main current circuit connection | Box terminal |
| Auxiliary and control circuit connection | Spring-loaded terminals |
| Front protection | IP20 |
| Product lifecycle | Start of final year of support |
Frequently Asked Questions
What exact model should be confirmed for this soft starter?
Confirm the complete order number 3RW4424-3BC44 and the SIRIUS product designation Soft starter.
What are the current and power values at 400 V?
At 40 °C, rated operational current is 47 A and motor power is 22 kW in standard circuit; inside-delta circuit values are 81 A and 45 kW.
Which control supply and terminals does the configuration use?
The control supply is 230 V AC at 50 Hz and 60 Hz. The main current circuit uses box terminals, while auxiliary and control circuits use spring-loaded terminals.
How is the unit mounted and protected?
It uses screw fixing on a vertical mounting surface, with the stated rotation and tilt limits. Front protection is IP20, with finger-safe protection for vertical contact from the front.
What lifecycle information should be checked for this part?
The supplied lifecycle data states: Start of final year of support. Confirm the required lifecycle status for the requested 3RW4424-3BC44.