Product Description
Key Features
- Exact product identity: SINAMICS G120C, order number 6SL3210-1KE23-8AF1; lifecycle: Active Product.
- Rated power and overload: Rated output power: 18.50 kW at low overload and 15.00 kW at high overload. Low overload: 150% for 3 s, 110% for 57 s, 100% for 240 s; high overload: 200% for 3 s, 150% for 57 s, 100% for 240 s.
- Supply and output: Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Output: 3 AC, 400V IEC | 480V NEC.
- Communication and I/O: Communication: PROFINET and EtherNet/IP. I/O: 6 standard digital inputs, 1 fail-safe digital input, 2 digital outputs, 1 differential analog/digital input and 1 non-isolated analog output.
- Control and safety: Supports V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law and sensorless vector control. Safe Torque Off is integrated.
- Connections and protection: Plug-in screw terminals are provided on the line side, motor end and DC link for a braking resistor. Protection: IP20 / UL open type; frame size FSC.
Technical Summary
| Product | SINAMICS G120C |
|---|---|
| Order number | 6SL3210-1KE23-8AF1 |
| Product lifecycle | Active Product |
| Input | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
| Rated output power (LO) | 18.50 kW | 25.00 hp |
| Rated output power (HO) | 15.00 kW | 20.00 hp |
| Communication | PROFINET, EtherNet/IP |
| I/O | 6DI, 2DO, 1AI, 1AO, 1 fail-safe digital input |
| Protection | IP20 / UL open type |
| Frame size | FSC |
Frequently Asked Questions
What exact Siemens model should be confirmed for this drive?
Confirm order number 6SL3210-1KE23-8AF1 and the SINAMICS G120C product identity.
What are the low-overload and high-overload output ratings?
Low overload is 18.50 kW; high overload is 15.00 kW. The supplied overload sequences are 150% for 3 s, 110% for 57 s, 100% for 240 s at low overload, and 200% for 3 s, 150% for 57 s, 100% for 240 s at high overload.
Which communication interface and I/O are supplied?
Communication is PROFINET and EtherNet/IP. The supplied I/O includes 6 standard digital inputs, 1 fail-safe digital input, 2 digital outputs, 1 differential analog/digital input and 1 non-isolated analog output.
What connections and protection details should be checked?
Check the plug-in screw terminals on the line side, motor end and DC link for a braking resistor. Protection is IP20 / UL open type, with frame size FSC.