Siemens Industrial Automation

6SL3210-1KE15-8AB2

6SL3210-1KE15-8AB2 is a Siemens SINAMICS G120C converter with 3 AC 380 ... 480 V input, 2.20 kW LO rated power, IP20 and USS/MODBUS RTU. Check this legacy-part request.

Complete Product Information
Product Code
6SL3210-1KE15-8AB2
Dimensions
22.5 × 27 × 8.5 cm
Weight
1.3 kg
Lifecycle
Active Product
Availability
Check availability with quotation
Lead Time
Confirmed with quotation
Product Attachment
Download technical file

Availability, lead time, condition and warranty are confirmed for each quotation.

Product Information

Technical Product Information

Product Description

Key Features

  • Exact product identity: Siemens SINAMICS G120C, order number 6SL3210-1KE15-8AB2; lifecycle: Active Product.
  • Rated input and output: Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Output rated power: 2.20 kW LO or 1.50 kW HO.
  • Overload ratings: LO: 150% for 3s, 110% for 57s, 100% for 240s. HO: 200% for 3s, 150% for 57s, 100% for 240s.
  • I/O interface: 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential input and 1 non-isolated analog output.
  • Communication and control: Communication: USS/MODBUS RTU. Supported control: V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law and sensorless vector control.
  • Connections and protection: Plug-in screw terminals are provided on the line side, motor end and DC link. Protection: IP20 / UL open type; integrated filter: Class A.

Technical Summary

Product Siemens SINAMICS G120C, 6SL3210-1KE15-8AB2
Lifecycle Active Product
Input 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz
Rated power (LO) 2.20 kW | 3.00 hp
Rated power (HO) 1.50 kW | 2.00 hp
Rated current (LO) 5.60 A
Rated current (HO) 4.10 A
Communication USS/MODBUS RTU
I/O 6DI, 2DO, 1AI, 1AO, 1 fail-safe digital input
Protection IP20 / UL open type
Frame size FSAA

Frequently Asked Questions

What input rating should be confirmed for 6SL3210-1KE15-8AB2?

Confirm 3 AC input, 380 … 480 V +10 % -20 %, and 47 … 63 Hz.

What are the LO and HO rated powers?

LO rated power is 2.20 kW | 3.00 hp; HO rated power is 1.50 kW | 2.00 hp.

Which communication interface does this converter have?

It has USS/MODBUS RTU communication.

Does this configuration include encoder feedback?

No. Vector control with sensor, encoderless torque control and torque control with encoder are marked No.

Product Information

RFQ Information

When contacting us by email, include the model or part number, quantity, brand, specifications and destination. Product or nameplate photos can help identify the requested item.

01Which product reference should I send?

Send the complete model, order number or MLFB shown on the product. Include the hardware version when it matters.

02How are supply terms confirmed?

Availability, condition, lead time, warranty and delivery terms are stated for the specific quotation.

03What helps with replacement requests?

Share the installed model, application, electrical and mechanical requirements, communication interface and a clear nameplate photo.

Product RFQ

Send the Details Needed for a Quotation

Use the form for the product model, quantity and contact details. Add the destination and technical questions in the message.

When contacting us by email, include the model or part number, quantity, brand, specifications and destination. Product or nameplate photos can help identify the requested item.

Email Your Requirement

* Email is required. Other fields are optional, but more detail helps us respond accurately.

Request a Quote