- PROFINET to CAN/CANopen gateway: SIMATIC PN/CAN LINK Gateway from PROFINET to CAN or CANopen networks; supports CAN Standard CAN 2.0A/B and CANopen Manager / Slave acc. to CiA.
- Communication interfaces: PROFINET interface with 2 RJ45 ports and integrated switch; CAN interface with 1 9-pin sub D socket.
- Supply and protection: Rated supply voltage: 24 V DC, permissible range 20.4 V to 28.8 V; reverse polarity, overvoltage, and short-circuit protection: Yes; IP degree of protection: IP20.
- Firmware and engineering: Firmware version: V2.4.0; FW update possible: Yes; configurable/integrated in STEP 7 TIA Portal from STEP 7 V14 or higher.
- DIN rail installation: Mounting: DIN rail, wall mounting, portrait mounting; rail mounting and control cabinet installation: Yes; recommended mounting position: Horizontal.
- CAN communication capacity: CAN transmission rate: 50 kbit/s to 1 000 kbit/s; maximum number of devices: 126; number of PDOs: 512 Send / receive.
Applications
- PROFINET-to-CAN network communication: Provides communication from PROFINET to CAN or CANopen networks, including CANopen Manager / Slave functions acc. to CiA 301 & CiA 302.
Technical Summary
| Product type | PN/CAN Link |
|---|---|
| Firmware version | V2.4.0 |
| PROFINET transmission rate, max. | 100 Mbit/s |
| PROFINET RJ45 ports | 2 |
| CAN operating modes | CAN Standard CAN 2.0A/B; CANopen Manager / Slave acc. to CiA |
| CAN transmission rate | 50 kbit/s to 1 000 kbit/s |
| CAN maximum number of devices | 126 |
| CAN connection | 1 9-pin sub D socket |
| Rated supply voltage | 24 V DC |
| Supply voltage permissible range | 20.4 V to 28.8 V |
| Mounting | DIN rail, wall mounting, portrait mounting |
| IP degree of protection | IP20 |
Frequently Asked Questions
What exact Siemens model should be confirmed for this PN/CAN Link Gateway?
Confirm Siemens 6BK1620-0AA00-0AA0 and product type designation PN/CAN Link.
Which networks does the Siemens 6BK1620-0AA00-0AA0 connect?
It provides communication from PROFINET to CAN or CANopen networks and supports CAN Standard CAN 2.0A/B and CANopen Manager / Slave acc. to CiA.
What supply voltage does this gateway require?
Rated supply voltage is 24 V DC, with a permissible range of 20.4 V to 28.8 V.
How is the gateway mounted?
It supports DIN rail, wall mounting, and portrait mounting. Rail mounting and control cabinet installation are supported.