Product Description
Key Features
- Exact SIPLUS configuration: SIPLUS S7-300 SM 332 based on 6ES7332-5HF00-0AB0, with conformal coating and 40-pole connection.
- Analog output capacity: Has 8 analog outputs; 4 outputs are available at +70 °C.
- Output signal ranges: Supports 0 to 10 V, 1 V to 5 V, -10 V to +10 V, 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
- Supply and protection: Load voltage L+ is 24 V rated DC, with reverse polarity protection. Voltage outputs have short-circuit protection.
- Diagnostics: Has parameterizable diagnostics, substitute values, and diagnostic alarms, plus readable diagnostic information and a red Group error SF LED.
- Installation and connection: Removing and inserting with the active backplane bus is possible. Voltage outputs use four-wire actuator connections; current outputs use two-wire connections.
Applications
- Analog voltage output: Provides analog voltage output signals across the supported voltage ranges.
- Analog current output: Provides analog current output signals across the supported current ranges.
- Output diagnostics: Provides diagnostic information, diagnostic alarms, and parameterizable substitute values.
Technical Summary
| Product lifecycle | Product cancellation |
|---|---|
| Product family | SIPLUS S7-300 SM 332 |
| Based on | 6ES7332-5HF00-0AB0 |
| Analog outputs | 8; 4 @ +70 °C |
| Load voltage L+ | Rated value (DC): 24 V |
| Output ranges | 0 to 10 V; 1 V to 5 V; -10 V to +10 V; 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Resolution with overrange | 12 bit; ±10 V, ±20 mA, 4 mA to 20 mA, 1 V to 5 V: 11 bit + sign; 0 V to 10 V, 0 mA to 20 mA: 12 bit |
| Conversion time per channel | 0.8 ms |
| Connection of actuators | Voltage output: four-wire connection; current output: two-wire connection |
| Diagnostics | Diagnostics, substitute values, and diagnostic alarms: Yes; Parameterizable |
| Installation | Removing and inserting with active backplane bus possible |
Frequently Asked Questions
What lifecycle status applies to 6AG1332-5HF00-2AB0?
Its lifecycle status is Product cancellation.
How are the analog outputs connected?
Voltage outputs use a four-wire actuator connection, and current outputs use a two-wire actuator connection.
Can the module be removed or inserted while the backplane bus is active?
Yes, removing and inserting with the active backplane bus is possible.
What diagnostic functions are available?
Diagnostics, substitute values, and diagnostic alarms are parameterizable; diagnostic information is readable, and a red Group error SF LED is provided.