Product Description
Key Features
- Exact product identity: SIMATIC ET 200SP analog input module, product type designation AI 8xRTD/TC 2-wire HF, with Color code CC00.
- Analog input capacity: 8 analog inputs with 16 bit resolution including sign for the listed voltage, thermocouple, resistance thermometer and resistor ranges.
- Supply and protection: Rated supply: 24 V DC; permissible range: 19.2 V to 28.8 V DC. Reverse polarity protection is provided.
- Engineering and firmware: Firmware version V2.1; FW update possible. STEP 7 TIA Portal is configurable/integrated from V16, V17 / V18.
- Diagnostics: Channel diagnostics, diagnostic alarm, wire-break detection channel by channel, group error, overflow/underflow channel by channel, and green/red DIAG LED.
- Installation and dimensions: Suitable for BU type A0, A1 with Type A mechanical coding element. Dimensions: 15 mm width, 73 mm height, 58 mm depth.
Applications
- Temperature measurement: Supports temperature measurement with thermocouple and resistance thermometer input ranges.
- Voltage, resistance and resistor measurement: Supports voltage measurement, resistance measurement with two-wire connection, and resistor input ranges.
Technical Summary
| Product type designation | AI 8xRTD/TC 2-wire HF |
|---|---|
| Product lifecycle | Active Product |
| Analog inputs | 8 |
| Resolution | 16 bit including sign |
| Rated supply | 24 V DC |
| Permissible supply range | 19.2 V to 28.8 V DC |
| Firmware version | V2.1 |
| Usable BaseUnits | BU type A0, A1 |
| Input connection | Voltage measurement; resistance measurement with two-wire connection |
| Channel diagnostics | Yes |
Frequently Asked Questions
What is the exact order number and product type?
The exact order number is 6ES7134-6JF00-0CA1, and the product type designation is AI 8xRTD/TC 2-wire HF.
Which BaseUnits are suitable for this module?
The module is suitable for BU type A0, A1.
What firmware and engineering versions are supplied?
Firmware version is V2.1. FW update is possible. STEP 7 TIA Portal is configurable/integrated from V16, V17 / V18; STEP 7 from V5.5 SP3 / V5.5 SP4; PCS 7 from V8.1 SP1.
Which connections does the module support?
It supports voltage measurement and resistance measurement with two-wire connection. Three-wire and four-wire resistance measurement are not supported.
What configuration should be confirmed for a part request?
Confirm the nameplate order number, firmware or version, required BaseUnit, connector and installed configuration, quantity, destination, and condition preference.