Product Description
Key Features
- Product identity: SIPLUS S7-300 SM 331 2AI HART based on 6ES7331-7TB00-0AB0 with conformal coating.
- Analog inputs: 2 analog inputs support rated current ranges of 0 to 20 mA and 4 mA to 20 mA, with 50 Ω input resistance for each range.
- Supply: Rated load voltage is 24 V DC. Transmitter supply is 15 V at 22 mA and is short-circuit proof at approximately 30 mA.
- HART and diagnostics: HART communication is active; diagnostics, diagnostic alarms, limit value alarms, overrange, wire-break, and short-circuit detection are supported.
- Ex(i) and protection: The module supports Ex(i) protection and has IP20 protection. Connecting-terminal maximums for gas group IIC include 26 V no-load voltage and 96.1 mA short-circuit current.
Applications
- Current measurement: Supports current measurement with 2-wire and 4-wire transducers.
- HART communication: Supports active HART communication for connected signal encoders.
- Signal diagnostics: Provides diagnostics for overrange, wire-break, short-circuit, and parameterizable alarms.
Technical Summary
| Product | 6AG1331-7TB00-7AB0 |
|---|---|
| Base product | 6ES7331-7TB00-0AB0 |
| Analog inputs | 2 |
| Rated load voltage | 24 V DC |
| Rated current ranges | 0 to 20 mA; 4 mA to 20 mA |
| Input resistance | 50 Ω |
| Transmitter supply | 15 V; at 22 mA |
| Resolution with overrange, max. | 16 bit; 10 bit to 15 bit + sign |
| HART communication | Active; green LED (H) |
| Operational error limit | 0.55 %; From 0/4 to 20 mA |
| Product lifecycle | Start of final year of support |
Frequently Asked Questions
What exact model should be confirmed for a 2AI HART module?
Confirm Siemens 6AG1331-7TB00-7AB0, SIPLUS S7-300 SM 331 2AI HART, based on 6ES7331-7TB00-0AB0.
What supply does this module use?
The rated load voltage is 24 V DC. Transmitter supply is 15 V at 22 mA.
Which signal encoder connections are supported?
Current measurement is supported with 2-wire and 4-wire transducers.
What diagnostics should be checked?
Check diagnostics for overrange, wire-break, short-circuit, HART communication, diagnostic alarms, and limit value alarms.
What lifecycle information should be confirmed?
The supplied lifecycle information is Start of final year of support; confirm the requested quantity, destination, condition preference, and requested date.