Product Description
Key Features
- Analog input configuration: 4 differential analog inputs for voltage measurement and 2-wire current measurement; 4-wire current measurement is not supported.
- Input ranges and resolution: Voltage ranges: 0 to +10 V, 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V; current ranges: 0 to 20 mA and 4 mA to 20 mA. Resolution is up to 16 bit including sign.
- Supply and protection: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection. Encoder supply is 24 V with short-circuit protection.
- Installation and dimensions: Suitable for BU type A0, A1 with 2-wire connection. Dimensions are 15 mm wide, 73 mm high, and 58 mm deep; weight is approximately 31 g.
- Diagnostics and identification: Module diagnostics, diagnostic alarm, supply-voltage monitoring, wire-break detection at 4 to 20 mA, short-circuit detection, Group error, and Overflow/Underflow are supported. The module has color code CC03 and I&M0 to I&M3 data.
- Lifecycle and environmental design: Product lifecycle: Announcement of product phase-out. The module has conformal coating and supports horizontal operation from -40 °C to 60 °C, with +70 °C for 10 minutes under OT1, ST1/ST2 conditions according to EN 50155.
Applications
- Rail vehicles: The source specifies railway applications, including EMC requirements for rail vehicles and railway-related systems.
- Industrial process technology: The source specifies use in industrial process technology and environmental conditions according to EN 60654-4 and ANSI/ISA-71.04.
- Land craft and special-purpose vehicles: The source specifies use on land craft, rail vehicles, and special-purpose vehicles.
Technical Summary
| Product type | AI 4x U/I 2-wire |
|---|---|
| Input channels | 4; Differential inputs |
| Rated supply | 24 V DC |
| Permissible supply range | 19.2 V to 28.8 V DC |
| Input ranges | 0 to +10 V; 1 V to 5 V; -10 V to +10 V; -5 V to +5 V; 0 to 20 mA; 4 mA to 20 mA |
| Resolution | 16 bit including sign, max. |
| BaseUnits | BU type A0, A1 |
| Firmware update | Yes; based on 6ES7134-6HD01-0BA1 |
| Product lifecycle | Announcement of product phase-out |
Frequently Asked Questions
What exact order number should be confirmed for this Siemens analog input module?
Confirm 6AG2134-6HD01-1BA1 on the nameplate or installed-part record.
Which BaseUnits and connection variant are supported?
The module supports BU type A0 and A1 with 2-wire connection.
What firmware information should be checked?
FW update is possible, and the module is based on 6ES7134-6HD01-0BA1.
What temperature and mounting details should be confirmed?
For horizontal installation, the ambient range is -40 °C to 60 °C, with +70 °C for 10 minutes under OT1, ST1/ST2 conditions according to EN 50155. Vertical installation is -40 °C to 50 °C.
What lifecycle information is supplied for this configuration?
The supplied lifecycle information is Announcement of product phase-out.