- Exact product identity: SIMATIC DP electronics module for ET 200SP; product type designation: F-DQ 4x24VDC/2A PM HF.
- Digital outputs: 4 parameterizable transistor digital outputs with short-circuit protection, open-circuit detection, and overload protection.
- Output ratings: Rated output voltage: 24 V DC. Rated output current for signal "1": 2 A; maximum current per module: 6 A, with derating data in the manual.
- Supply and power: Rated supply voltage: 24 V DC, permissible range 19.2 V to 28.8 V. Current consumption: 75 mA without load; power consumption from the backplane bus: 70 mW.
- Engineering and communication: Configurable/integrated with STEP 7 TIA Portal from V12, STEP 7 from V5.5 SP3 / -, and PROFINET from GSD revision V2.31.
- Lifecycle and installation data: Lifecycle: Active Product. Usable BaseUnits: BU type A0; width: 15 mm; packaging dimensions: 7.50 x 6.90 x 2.90 cm.
Applications
- Controlling a digital input: The digital output can control a digital input according to IEC 61131-2, type 2.
Technical Summary
| Order number | 6ES7136-6DB00-0CA0 |
|---|---|
| Product type designation | F-DQ 4x24VDC/2A PM HF |
| Product family | SIMATIC DP electronics module for ET 200SP |
| Digital outputs | 4 parameterizable transistor outputs |
| Rated output voltage | 24 V DC |
| Rated output current for signal "1" | 2 A |
| Maximum current per module | 6 A; note derating data in the manual |
| Supply voltage | 24 V DC; permissible range 19.2 V to 28.8 V |
| Usable BaseUnits | BU type A0 |
| Engineering with STEP 7 TIA Portal | Configurable/integrated from V12 |
| Engineering with PROFINET | From GSD revision V2.31 |
| Lifecycle | Active Product |
Frequently Asked Questions
What is the exact order number and product type?
The order number is 6ES7136-6DB00-0CA0, and the product type designation is F-DQ 4x24VDC/2A PM HF.
How many digital outputs does the module have?
It has 4 parameterizable transistor digital outputs.
What supply voltage does this module use?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V.
Which engineering versions are supported?
STEP 7 TIA Portal is configurable/integrated from V12, STEP 7 from V5.5 SP3 / -, and PROFINET from GSD revision V2.31.