Siemens Industrial Automation

6SL3210-1KE13-2UB2

6SL3210-1KE13-2UB2 Siemens SINAMICS G120C drive with 3 AC 380 ... 480 V input, 1.10 kW LO output, IP20 protection and USS/MODBUS RTU. Request exact legacy-part verification.

Complete Product Information
Product Code
6SL3210-1KE13-2UB2
Dimensions
22.5 × 27 × 8.5 cm
Weight
1.1 kg
Lifecycle
Active Product
Availability
Check availability with quotation
Lead Time
Confirmed with quotation
Product Attachment
Download technical file

Availability, lead time, condition and warranty are confirmed for each quotation.

Product Information

Technical Product Information

Product Description

Key Features

  • Rated input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz; rated current is 4.10 A for LO and 3.20 A for HO.
  • Overload output ratings: Low overload: 1.10 kW at 150% for 3s, 110% for 57s, and 100% for 240s. High overload: 0.75 kW at 200% for 3s, 150% for 57s, and 100% for 240s.
  • I/O and safety: The unfiltered external 24 V I/O interface has 6DI, 2DO, 1AI, and 1AO; 1 fail-safe digital input and integrated Safe Torque Off are supplied.
  • Communication and control: Fieldbus: USS/MODBUS RTU. Supported control techniques include V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law, and sensorless vector control.
  • Connections and protection: Plug-in screw terminals are provided on the line side, motor end, and DC link for a braking resistor. Protection is IP20 / UL open type; frame size is FSAA.

Technical Summary

Product Siemens SINAMICS G120C, 6SL3210-1KE13-2UB2
Lifecycle Active Product
Input 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz
Output power (LO) 1.10 kW | 1.50 hp
Output power (HO) 0.75 kW | 1.00 hp
I/O interface Unfiltered external 24 V; 6DI, 2DO, 1AI, 1AO
Communication USS/MODBUS RTU
Safety Integrated Safe Torque Off; 1 fail-safe digital input
Protection IP20 / UL open type

Frequently Asked Questions

What exact input ratings should be confirmed for 6SL3210-1KE13-2UB2?

Confirm 3 AC input, 380 … 480 V +10 % -20 %, 47 … 63 Hz, and rated current of 4.10 A for LO or 3.20 A for HO.

Which overload configuration does this drive provide?

Low overload is 1.10 kW at 150% for 3s, 110% for 57s, and 100% for 240s. High overload is 0.75 kW at 200% for 3s, 150% for 57s, and 100% for 240s.

What communication, I/O, and safety interfaces should be checked?

Check USS/MODBUS RTU, the unfiltered external 24 V I/O interface with 6DI, 2DO, 1AI, and 1AO, plus 1 fail-safe digital input and integrated Safe Torque Off.

Which connections and mechanical details should be matched?

Match the plug-in screw terminals, FSAA frame size, IP20 / UL open type protection, 73 mm width, and 155 mm depth.

Product Information

RFQ Information

When contacting us by email, include the model or part number, quantity, brand, specifications and destination. Product or nameplate photos can help identify the requested item.

01Which product reference should I send?

Send the complete model, order number or MLFB shown on the product. Include the hardware version when it matters.

02How are supply terms confirmed?

Availability, condition, lead time, warranty and delivery terms are stated for the specific quotation.

03What helps with replacement requests?

Share the installed model, application, electrical and mechanical requirements, communication interface and a clear nameplate photo.

Product RFQ

Send the Details Needed for a Quotation

Use the form for the product model, quantity and contact details. Add the destination and technical questions in the message.

When contacting us by email, include the model or part number, quantity, brand, specifications and destination. Product or nameplate photos can help identify the requested item.

Email Your Requirement

* Email is required. Other fields are optional, but more detail helps us respond accurately.

Request a Quote