Product Description
Key Features
- Energy meter identity and configuration: AI Energy Meter 480VAC ST analog input module, based on 6ES7134-6PA20-0BD0, suitable for BU type D0.
- Measurement functions: Measures voltage, current, energy, frequency, power, active power and reactive power; voltage and current measurement use TRMS.
- Voltage measurement range: Measurable line voltage is 277 V between phase and neutral conductor and 480 V between line conductors; maximum values are 293 V and 508 V respectively.
- Current measurement: Measurable relative AC current is 1 % to 100 % relative to the secondary rated current 5 A. Continuous AC current is 5 A, with a maximum permissible current of 1 A per phase at > +60 °C.
- Supply and cycle time: Rated supply voltage is AC 100 – 277 V, supplied via voltage measurement channel L1. Typical cycle time for all channels is 50 ms.
- Mounting and environmental design: Any mounting position; horizontal installation supports -40 °C to 70 °C, with +85 °C for 10 minutes under OT4, ST1/ST2 according to EN 50155. Conformal coating is Class 2 for high reliability.
Applications
- Voltage measurement: Measures line voltage between phase and neutral conductor and between line conductors.
- Current and energy measurement: Measures current, active energy and reactive energy using current-transformer inputs.
- Power and frequency measurement: Measures active power, reactive power, power factor and line frequency.
Technical Summary
| Product type | AI Energy Meter 480VAC ST |
|---|---|
| Based on | 6ES7134-6PA20-0BD0 |
| Usable BaseUnit | BU type D0 |
| Rated supply voltage (AC) | AC 100 – 277 V |
| Measurable line voltage | 277 V phase-to-neutral; 480 V between line conductors |
| Measurable relative AC current | 1 % to 100 % relative to the secondary rated current 5 A |
| Typical cycle time (all channels) | 50 ms |
| Measuring procedure | TRMS for voltage and current measurement |
| Mounting position | any |
| Operating temperature, horizontal installation | -40 °C to 70 °C; +85 °C for 10 min (OT4, ST1/ST2 according to EN 50155) |
| Product lifecycle | Active Product |
Frequently Asked Questions
What order number should be confirmed for this Siemens SIPLUS module?
Confirm the complete order number 6AG2134-6PA20-4BD0 on the installed part or nameplate.
Which BaseUnit is specified for 6AG2134-6PA20-4BD0?
The module is suitable for BU type D0.
What measurement functions does this module provide?
It provides voltage, current, energy, frequency, power, active power and reactive power measurement.
What supply voltage is specified?
The rated supply voltage is AC 100 – 277 V, supplied via voltage measurement channel L1.