Product Description
Key Features
- Exact SIPLUS identification: SIPLUS S7-1200 SB 1223 I/O based on 6ES7223-3AD30-0XB0; product type designation: SB 1223, DI 2×5 V DC/DQ 2×5 V DC 200 kHz.
- Digital I/O configuration: 2 current-sourcing digital inputs and 2 MOSFET solid-state digital outputs with current-sinking/current-sourcing; inputs and outputs are in groups of 2.
- 5 V DC electrical data: Input rated value: 5 V DC. Output rated value: 5 V DC; output switching capacity with resistive load, max. 0.1 A.
- Configurable timing: Standard inputs are parameterizable from 0.1 μs to 20.0 μs and from 0.05 ms to 20.0 ms; interrupt inputs and technological functions are parameterizable.
- Interfaces and installation: Shielded cable length, max. 50 m; LED diagnostics indicate input and output status. Dimensions are 38 mm wide, 62 mm high, and 21 mm deep.
- Environmental and lifecycle data: Conformal coating is provided for high reliability, with operation from -40 °C to 60 °C and start-up at -25 °C. Lifecycle: Active Product.
Technical Summary
| Product type | SB 1223, DI 2×5 V DC/DQ 2×5 V DC 200 kHz |
|---|---|
| Based on | 6ES7223-3AD30-0XB0 |
| Digital inputs | 2; Current-sourcing |
| Digital outputs | 2; MOSFET, solid-state (current-sinking/current-sourcing) |
| Input rated value | 5 V DC |
| Output rated value | 5 V DC |
| Output switching capacity | With resistive load, max. 0.1 A |
| Operating ambient temperature | -40 °C to 60 °C; start-up at -25 °C |
| Lifecycle | Active Product |
Frequently Asked Questions
What exact model should be confirmed for this Siemens SIPLUS I/O module?
Confirm product number 6AG1223-3AD30-5XB0 and the based-on designation 6ES7223-3AD30-0XB0.
How many digital inputs and outputs does the module have?
It has 2 current-sourcing digital inputs and 2 MOSFET solid-state digital outputs with current-sinking/current-sourcing.
What signal voltage does the module use?
The rated input value and rated output value are both 5 V DC.
What cable length and mounting dimensions should be checked?
The shielded cable length is max. 50 m. Dimensions are 38 mm wide, 62 mm high, and 21 mm deep.
What environmental configuration should be confirmed?
Operation is from -40 °C to 60 °C, with start-up at -25 °C; the module has conformal coating and horizontal installation is specified for the stated 100% RH condition.