Siemens Industrial Automation

6ES7193-6AG50-0AA0

Siemens 6ES7193-6AG50-0AA0 SIMATIC BusAdapter BA 2xLC-LD has 2 LC ports for single-mode fiber-optic cable up to 20 km. Active Product. Submit a legacy-part verification inquiry.

Complete Product Information
Product Code
6ES7193-6AG50-0AA0
Dimensions
7.7 × 6.5 × 2.3 cm
Weight
0.075 kg
Lifecycle
Active Product
Availability
Check availability with quotation
Lead Time
Confirmed with quotation
Product Attachment
Download technical file

Availability, lead time, condition and warranty are confirmed for each quotation.

Product Information

Technical Product Information

Product Description

Key Features

  • Product identity: SIMATIC BusAdapter BA 2xLC-LD with 2 LC-LD ports.
  • PROFINET interfaces: 1 PROFINET interface with 2 ports (switch) for 2x LC-LD single-mode fiber-optic cable.
  • Fiber-optic range: Single-mode fiber-optic cable 9/125 μm: 20 km; 10 km for topology or IRT configuration.
  • Optical specifications: Wavelength: 1 270 … 1 380 nm, corresponding to 100BASE-LX; min. transmit power: -15 dB; min. receiver sensitivity: -28 dB.
  • Installation limits: During operation, ambient temperature is -30 °C to 60 °C for horizontal installation and -30 °C to 50 °C for vertical installation.
  • Product lifecycle: Lifecycle status: Active Product.

Applications

  • PROFINET IO communication: Provides a PROFINET interface through 2 LC-LD ports for single-mode fiber-optic cable.

Technical Summary

Product 6ES7193-6AG50-0AA0
Product type BA 2x LC-LD
PROFINET interface 1; 2 ports (switch) 2x LC-LD single-mode fiber-optic cable
LC ports 2; wavelength of 1 270 … 1 380 nm, corresponds to 100BASE-LX
Fiber-optic cable Single-mode fiber-optic cable 9/125 μm
Optical power Min. transmit power -15 dB; min. receiver sensitivity -28 dB
Operating temperature, horizontal installation -30 °C to 60 °C
Operating temperature, vertical installation -30 °C to 50 °C
Maximum installation altitude 5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200SP system manual
Lifecycle Active Product

Frequently Asked Questions

What order number should be confirmed for this SIMATIC BusAdapter?

Confirm the complete order number 6ES7193-6AG50-0AA0.

How many LC ports does the BA 2xLC-LD have?

It has 2 LC-LD ports in 1 PROFINET interface, configured as a switch.

What fiber-optic cable and distance are supported?

It supports single-mode fiber-optic cable 9/125 μm up to 20 km, or 10 km for topology or IRT configuration.

What operating temperature applies to the adapter?

The range is -30 °C to 60 °C for horizontal installation and -30 °C to 50 °C for vertical installation.

Product Information

RFQ Information

When contacting us by email, include the model or part number, quantity, brand, specifications and destination. Product or nameplate photos can help identify the requested item.

01Which product reference should I send?

Send the complete model, order number or MLFB shown on the product. Include the hardware version when it matters.

02How are supply terms confirmed?

Availability, condition, lead time, warranty and delivery terms are stated for the specific quotation.

03What helps with replacement requests?

Share the installed model, application, electrical and mechanical requirements, communication interface and a clear nameplate photo.

Product RFQ

Send the Details Needed for a Quotation

Use the form for the product model, quantity and contact details. Add the destination and technical questions in the message.

When contacting us by email, include the model or part number, quantity, brand, specifications and destination. Product or nameplate photos can help identify the requested item.

Email Your Requirement

* Email is required. Other fields are optional, but more detail helps us respond accurately.

Request a Quote