Product Description
Key Features
- Interface module identity: SIMATIC ET 200SP, PROFINET interface module IM 155-6PN/3 HF with 2 slots for BusAdapter.
- Module capacity: Supports up to 64 ET 200SP modules, 16 ET 200AL modules, and 256 submodules per station.
- PROFINET interfaces: Provides 1 PROFINET interface with 3 switch ports, 100BASE-TX transmission, and RJ45 with BusAdapter.
- Supply and protection: Rated supply voltage: 24 V DC; permissible range: 19.2 V to 28.8 V DC. Reverse polarity and short-circuit protection are included.
- Firmware and lifecycle: Firmware version: V4.2. Firmware update is possible. Product lifecycle: Active Product.
Applications
- Tool changing: Supports tool changer functions with docking station and docking unit.
- Local coupling: Supports local coupling with I/O data.
Technical Summary
| Product type designation | IM 155-6 PN/3 HF |
|---|---|
| Firmware version | V4.2 |
| PROFINET interfaces | 1; 3 ports (switch) |
| Supported ET 200SP modules, max. | 64 |
| Supported ET 200AL modules, max. | 16 |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Address space per module, max. | 288 byte; for input and output data respectively |
| Isochronous mode | Yes; shortest clock pulse 250 μs; max. cycle 4 ms |
| Product lifecycle | Active Product |
Frequently Asked Questions
What order number and product type should be confirmed?
Confirm order number 6ES7155-6AU30-0CN0 and product type designation IM 155-6 PN/3 HF.
Which firmware version does this interface module have?
Firmware version is V4.2, and firmware update is possible.
Which PROFINET connector configuration should be checked?
The module has 1 PROFINET interface with 3 switch ports and RJ45 with BusAdapter. The BusAdapter is not a single fixed connector configuration.
What is the supplied lifecycle status?
The supplied lifecycle status is Active Product.