Product Description
Key Features
- Analog output identity: Product type designation: AQ 8xU/I HS; 8 analog outputs with voltage and current output ranges.
- Resolution and oversampling: Resolution with overrange: 16 bit; oversampling is supported with up to 16 values per cycle and 125 μs minimum resolution.
- Supply and current: Rated supply voltage: 24 V DC; permissible range: 19.2 V to 28.8 V DC. Maximum current consumption is 320 mA with 19.2 V supply.
- Diagnostics and protection: Diagnostics, diagnostic alarm, supply-voltage monitoring, substitute values, wire-break detection for current output, and short-circuit detection for voltage output are supported.
- Connections and loads: Voltage outputs support two-wire and four-wire actuator connections; current outputs support two-wire connections. Minimum voltage-output load impedance is 1 kΩ.
- Supplied lifecycle data: Lifecycle status: Active Product. Firmware version: V2.1.0; firmware updates are possible.
Applications
- Safety-oriented load-group shutdown: Supports safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015.
Technical Summary
| Product type | AQ 8xU/I HS |
|---|---|
| Analog outputs | 8 |
| Resolution with overrange | 16 bit |
| Rated supply voltage | 24 V DC |
| Permissible supply range | 19.2 V to 28.8 V DC |
| Cycle time (all channels), min. | 125 μs; independent of number of activated channels |
| Output ranges | 0 to 10 V; 1 V to 5 V; -10 V to +10 V; 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Firmware version | V2.1.0 |
| Product lifecycle | Active Product |
| Safety shutdown capability | Up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015 |
Frequently Asked Questions
What exact order number should be confirmed for this analog output module?
Confirm 6ES7532-5HF00-0AB0 and product type AQ 8xU/I HS.
What supply voltage does the module use?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
Which output ranges and actuator connections are supported?
Supported ranges are 0 to 10 V, 1 V to 5 V, -10 V to +10 V, 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA. Voltage outputs support two-wire and four-wire connections; current outputs support two-wire connections.
What is included in the selected configuration?
It includes the infeed element, shielding bracket, and shield terminal. The front connector with screw terminals or push-in terminals is ordered separately.