Siemens Industrial Automation

6AG1331-7PF01-4AB0

6AG1331-7PF01-4AB0 Siemens SIPLUS S7-300 SM 331 with 8 isolated analog inputs, resistance measurement and 24 V supply. Request exact-part verification.

Complete Product Information
Product Code
6AG1331-7PF01-4AB0
Dimensions
13 × 15 × 4.8 cm
Weight
0.339 kg
Lifecycle
Product cancellation
Availability
Check availability with quotation
Lead Time
Confirmed with quotation
Product Attachment
Download technical file

Availability, lead time, condition and warranty are confirmed for each quotation.

Product Information

Technical Product Information

Product Description

Key Features

  • Product identity: SIPLUS S7-300 SM 331 based on 6ES7331-7PF01-0AB0, with conformal coating and 8 analog inputs.
  • Resistance measurement: Supports resistance thermometers and resistance measurement, including Cu 10, Ni 100/120/200/500/1000, Pt 100/200/500/1000 and 0 to 150/300/600 ohms.
  • Signal connections: Supports resistance measurement with two-wire connection without resistance correction, three-wire connection and four-wire connection.
  • Supply and protection: Load voltage L+ rated value: 24 V DC. Reverse polarity protection: Yes; input current from load voltage L+ max.: 240 mA.
  • Diagnostics and isolation: Parameterizable diagnostics, diagnostic and limit value alarms, hardware interrupt on channels 0 to 7, and isolation between analog inputs and the backplane bus.

Technical Summary

Product name 6AG1331-7PF01-4AB0
Based on 6ES7331-7PF01-0AB0
Analog inputs 8
Resistance measurement 8 inputs
Load voltage L+ rated value 24 V DC
Reverse polarity protection Yes
Input current from load voltage L+ max. 240 mA
Resistance measurement connections 2-wire without resistance correction; 3-wire; 4-wire
Resolution with overrange 16 bit; Two's complement
Product lifecycle Product cancellation

Frequently Asked Questions

What input capacity should be confirmed for 6AG1331-7PF01-4AB0?

It has 8 analog inputs, and 8 inputs are available for resistance measurement.

Which resistance measurement connections does this configuration support?

It supports two-wire connection without resistance correction, three-wire connection and four-wire connection.

What supply and reverse-polarity details should be checked?

Load voltage L+ has a rated value of 24 V DC, and reverse polarity protection is available.

Does this configuration include voltage, current or thermocouple input ranges?

No. Voltage, current and thermocouple input ranges are marked No; resistance thermometer and resistance input ranges are marked Yes.

Product Information

RFQ Information

When contacting us by email, include the model or part number, quantity, brand, specifications and destination. Product or nameplate photos can help identify the requested item.

01Which product reference should I send?

Send the complete model, order number or MLFB shown on the product. Include the hardware version when it matters.

02How are supply terms confirmed?

Availability, condition, lead time, warranty and delivery terms are stated for the specific quotation.

03What helps with replacement requests?

Share the installed model, application, electrical and mechanical requirements, communication interface and a clear nameplate photo.

Product RFQ

Send the Details Needed for a Quotation

Use the form for the product model, quantity and contact details. Add the destination and technical questions in the message.

When contacting us by email, include the model or part number, quantity, brand, specifications and destination. Product or nameplate photos can help identify the requested item.

Email Your Requirement

* Email is required. Other fields are optional, but more detail helps us respond accurately.

Request a Quote