Product Description
Key Features
- Analog input identity: Product type designation: AI 2xU/I 2-/4-wire HF; 2 differential analog inputs support voltage and current measurement.
- Input ranges and resolution: Voltage ranges include 0 to +10 V, 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V; current ranges include 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA, with up to 16 bit resolution.
- Supply and protection: Rated supply: 24 V DC, permissible range 19.2 V to 28.8 V, with reverse polarity protection. Encoder supply has short-circuit protection.
- System integration: Usable BaseUnits: BU type A0, A1. STEP 7 TIA Portal configuration is supported from V13; PROFINET uses GSDML V2.3.
- Diagnostics and operating functions: Channel diagnostics, diagnostic alarms, limit value alarms, wire-break detection for 4 to 20 mA, and overflow/underflow detection are supported. Reparameterization and calibration are possible in RUN.
- Physical and temperature data: Module dimensions: 15 mm width, 73 mm height, and 58 mm depth; weight: approx. 32 g. Operating temperature is -30 °C to 60 °C for horizontal installation and -30 °C to 50 °C for vertical installation.
Technical Summary
| Product type designation | AI 2xU/I 2-/4-wire HF |
|---|---|
| Number of analog inputs | 2; Differential inputs |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Maximum resolution | 16 bit |
| Usable BaseUnits | BU type A0, A1 |
| PROFINET GSD version | GSDML V2.3 |
Frequently Asked Questions
What exact order number should be confirmed for this analog input module?
Confirm the nameplate order number: 6ES7134-6HB00-0CA1.
Which BaseUnits and connection variants are supported?
BU type A0 and BU type A1 are supported for both 2-wire and 4-wire connections.
What firmware and engineering versions should be checked?
Firmware update is possible. STEP 7 TIA Portal is configurable/integrated from V13, STEP 7 from V5.5 / -, and PCS 7 from V8.1 SP1.