Product Description
Key Features
- Exact product identity: SINAUT ST7, TIM 3V-IE; SIPLUS brand, based on 6NH7800-3BA00.
- Communication interfaces: One RS-232 interface for SINAUT communication via a classic wide area network and one RJ45 interface for SINAUT communication via an IP-based network (WAN or LAN).
- Supply and consumption: 24 V DC supply; supply voltage 20.4 … 28.8 V; maximum current consumption is 0.2 A from the backplane bus and 0.2 A from the external supply voltage; power loss: 5.8 W.
- SINAUT communication: Supports SINAUT ST1 and SINAUT ST7 protocols, with a maximum of 12 S7 communication connections, including up to 4 PG connections and 8 OP connections.
- Module format and protection: Compact module S7-300 single width; 40 mm wide, 125 mm high, 120 mm deep; IP20 protection class; conformal coating, class A.
- Lifecycle status: Product cancellation.
Applications
- SINAUT communication via WAN or LAN: Provides SINAUT communication through one RS-232 interface for a classic wide area network and one RJ45 interface for an IP-based network.
- Substation communication: The source specifies suitability for use as a substation.
- TIM control center communication: The source specifies suitability for use as a TIM control center.
Technical Summary
| Product type | SINAUT ST7, TIM 3V-IE |
|---|---|
| Supply | 24 V DC; 20.4 … 28.8 V |
| Interfaces | 1 RS-232; 1 RJ45 port |
| Industrial Ethernet transfer rate | 10 … 100 Mbit/s |
| RS-232 transfer rate | 50 … 38400 bit/s |
| S7 communication connections | 12 maximum; 4 PG connections and 8 OP connections maximum |
| Module format | Compact module S7-300 single width |
| Protection class | IP20 |
| Ambient temperature during operation | -25 … +70 °C |
| Lifecycle | Product cancellation |
Frequently Asked Questions
What interfaces should be confirmed for Siemens 6AG1800-3BA00-7AA0?
The module has one RS-232 interface with a 9 pin Sub-D-connector and one Industrial Ethernet interface with an RJ45 port.
What supply voltage does 6AG1800-3BA00-7AA0 use?
Supply is 24 V DC, with a stated range of 20.4 … 28.8 V.
What is the S7 communication capacity?
The module supports a maximum of 12 S7 communication connections, including a maximum of 4 PG connections and 8 OP connections.
What lifecycle data applies to this exact order number?
Product cancellation.