Product Description
Key Features
- Exact interface module identity: SIPLUS ET 200SP IM155-6PN HF, order number 6AG1155-6AU01-2CN0, based on 6ES7155-6AU01-0CN0.
- PROFINET interface: 1 PROFINET interface with 2 ports via BusAdapter and integrated switch; PROFINET IO Device, PROFINET MRP and PROFINET system redundancy (S2) are supported.
- Module capacity: Maximum 64 modules per rack plus 16 ET 200AL modules; maximum 256 submodules per station.
- Supply and protection: Rated supply voltage: 24 V DC; permissible range: 19.2 V to 28.8 V DC; reverse polarity protection: Yes.
- Hot swapping and isochronous mode: Multi-hot swapping and isochronous mode are supported; shortest clock pulse: 250 μs, maximum cycle: 4 ms.
- Configuration and lifecycle: Includes server module 6AG1193-6PA00-7AA0. Optional PN strain relief is not included. Product lifecycle: Announcement of product phase-out.
Applications
- Tool changing: Supports a tool changer with docking station and docking unit.
Technical Summary
| Product type designation | IM 155-6 PN/2 HF |
|---|---|
| Supply voltage | 24 V DC; permissible range: 19.2 V to 28.8 V DC |
| PROFINET interfaces | 1; 2 ports via BusAdapter |
| Module capacity | 64 modules per rack; + 16 ET 200AL modules |
| PROFINET system redundancy | S2: Yes; NAP S2 |
| Hot swapping | Yes; Multi-hot swapping |
| Isochronous mode | Shortest clock pulse: 250 μs; maximum cycle: 4 ms |
| Current consumption, max. | 700 mA |
| Power loss, typ. | 2.4 W |
| Firmware update | Possible: Yes |
| Product lifecycle | Announcement of product phase-out |
Frequently Asked Questions
What order number should be confirmed for this SIPLUS interface module?
Confirm order number 6AG1155-6AU01-2CN0 and product type designation IM 155-6 PN/2 HF.
Which PROFINET connector configuration does the module use?
It has 2 ports via BusAdapter and an integrated switch. Compatible BusAdapter options include BA 2x RJ45, BA 2x FC, BA 2x SCRJ, BA SCRJ / RJ45, BA SCRJ / FC, BA 2x LC, BA LC / RJ45 and BA LC / FC.
What capacity should be checked against the installed configuration?
The maximum is 64 modules per rack plus 16 ET 200AL modules, with a maximum of 256 submodules per station.
Is PN strain relief included in this configuration?
It is optional and is not included.