Product Description
Key Features
- Digital output identity: SIMATIC S7-300 SM 322 digital output module with 16 DO and isolated solid-state relay outputs.
- Supply and output current: Load voltage: 24 V; 24 / 48 DC, with a permissible range of 20.4 V to 57.6 V. Output current for signal "1": 0.5 A rated value.
- Protection and diagnostics: Reverse polarity protection: Yes. Short-circuit protection: No; to be provided externally. Parameterizable diagnostic function and diagnostic alarm are available.
- Isolation and connection: Potential separation is provided between channels, between channels and backplane bus by Optocoupler, and between channels and the power supply of the electronics. Required front connector: 40-pin.
- Physical data: Dimensions: 40 mm width, 125 mm height, and 120 mm depth. Weight, approx.: 260 g.
- Lifecycle status: Product cancellation.
Applications
- Digital input control: The digital outputs can control a digital input.
- Redundant load control: Two outputs can be switched in parallel for redundant control of a load.
Technical Summary
| Product identity | SIMATIC S7-300 SM 322 digital output module, 16 DO, solid-state relay |
|---|---|
| Load voltage | 24 V; 24 / 48 DC |
| Permissible load-voltage range | 20.4 V to 57.6 V |
| Output current for signal "1" | 0.5 A rated value |
| Output delay with resistive load | "0" to "1": 6 ms; "1" to "0": 3 ms |
| Required front connector | 40-pin |
| Potential separation | Between channels in groups of 1; between channels and backplane bus: Optocoupler |
| Isolation tested with | 1 500 V AC |
| Product lifecycle | Product cancellation |
Frequently Asked Questions
What is the exact order number of this digital output module?
The exact order number is 6ES7322-5GH00-0AB0.
How many digital outputs does it have?
It has 16 digital outputs with solid-state relays.
What front connector is required?
A 40-pin front connector is required.
Does it include short-circuit protection?
No. Short-circuit protection is to be provided externally.