Product Description
Key Features
- Relay output configuration: The module has 4 parameterizable relay outputs with current-sinking and current-sourcing capability.
- Output ratings: Maximum current is 5 A per channel and 20 A per module. Maximum contact switching capacity is 5 A with a resistive load and 2 A with an inductive load.
- Supply and protection: Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC and reverse polarity protection.
- BaseUnit connection: BU type B1 supports 2-wire connection, and BU type B0 supports 3-wire connection.
- Diagnostics and status: The module provides diagnostics, diagnostic alarms, supply-voltage monitoring, group error information, and a green/red DIAG LED.
- Firmware and engineering: Firmware updates are possible; usable BaseUnits are BU type B0 and B1. STEP 7 TIA Portal is configurable/integrated from V13 SP1.
Technical Summary
| Product type designation | RQ 4×120 V DC … 230 V AC/5 A NO MA ST |
|---|---|
| Product lifecycle | Active Product |
| Number of relay outputs | 4 |
| Rated supply voltage of relay coil L+ (DC) | 24 V |
| Current per channel, max. | 5 A |
| Current per module, max. | 20 A |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| usable BaseUnits | BU type B0, B1 |
| PROFINET from GSD version/GSD revision | GSDML V2.3 |
| STEP 7 TIA Portal configurable/integrated from version | V13 SP1 |
| Module diagnostics | Yes; green/red DIAG LED |
Frequently Asked Questions
What exact order number should be confirmed for this relay module?
Confirm the nameplate order number 6ES7132-6MD00-0BB1 and the product type designation RQ 4×120 V DC … 230 V AC/5 A NO MA ST.
Which BaseUnits are usable with this module?
Usable BaseUnits are BU type B0 and B1. BU type B1 supports 2-wire connection, while BU type B0 supports 3-wire connection.
What output and supply values should be checked?
The module has 4 relay outputs, with a maximum current of 5 A per channel and 20 A per module. Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
Which firmware and engineering versions are supported?
Firmware updates are possible. STEP 7 TIA Portal is configurable/integrated from V13 SP1, and STEP 7 is configurable/integrated from V5.5 SP3 / -.